SRB324LT 24V
SRB324LT 24V
Downloads
- Optional: Short-circuit recognition, Manual reset with edge detection in fail-safe circuit, Automatic reset function
- Suitable for the signal processing of outputs with contact sensors
- Suitable for signal processing of outputs connected to potentials (AOPDs), e.g. safety light grids/curtains
- 3 safety contacts, STOP 0;
2 safety contacts, STOP 1 (adjustable 1 … 30 s) - 3 Signalling outputs, 1 Auxiliary contact
Ordering data
Note (Delivery capacity) |
Elde mevcut değil! |
Product type description |
SRB324LT 24V |
Article number (order number) |
101204855 |
eCl@ss number, version 12.0 |
27-37-18-19 |
eCl@ss number, version 11.0 |
27-37-18-19 |
eCl@ss number, version 9.0 |
27-37-18-19 |
ETIM number, version 7.0 |
EC001449 |
ETIM number, version 6.0 |
EC001449 |
Approvals - Standards
Certificates |
TÜV cULus |
General data
Standards |
EN IEC 62061 EN ISO 13849-1 EN IEC 60947-5-1 EN IEC 60947-5-3 EN IEC 60947-5-5 EN IEC 61508 EN IEC 60204-1 EN IEC 60947-1 |
Climatic stress |
EN 60068-2-78 |
Housing material |
Plastik, fiber cam takviyeli termoplastik, havalandırılmış |
Gross weight |
480 g |
General data - Features
Electronic Fuse |
Evet |
Wire breakage detection |
Evet |
Cross-circuit detection |
Evet |
Removable Terminals |
Evet |
Start input |
Evet |
Feedback circuit |
Evet |
Automatic reset function |
Evet |
Reset edge detection |
Evet |
Earth connection detection |
Evet |
Integral system diagnostics, status |
Evet |
Number of auxiliary contacts |
1 |
Number of LEDs |
6 |
Number of normally closed (NC) |
2 |
Number of undelayed semi-conductor outputs with signaling function |
3 |
Number of safety contacts |
5 |
Number of signalling outputs |
3 |
Safety classification |
Vorschriften |
EN IEC 60947-5-1 EN IEC 61508 |
Stop-Category |
0 1 |
Safety classification - Relay outputs |
Performance Level, stop 0, up to |
e |
Performance Level, stop 1, up to |
d |
Category, Stop 0 |
4 |
Category, Stop 1 |
3 |
Diagnostic Coverage (DC) Level, Stop 0 |
≥ 99 % |
Diagnostic Coverage (DC) Level, Stop 1 |
> 60 |
PFH value, Stop 0 |
2,00 x 10⁻⁸ /h |
PFH value, Stop 1 |
2,00 x 10⁻⁷ /h |
Safety Integrity Level (SIL), Stop 0, suitable for applications in |
3 |
Safety Integrity Level (SIL), Stop 1, suitable for applications in |
2 |
Mission time |
20 Year(s) |
Common Cause Failure (CCF), minimum |
65 |
Mechanical data
Mechanical life, minimum |
10.000.000 Operations |
Mounting |
EN 60715 e uygun standart DIN rayının üzerine kilitlenir |
Mechanical data - Connection technique
Terminal designations |
IEC/EN 60947-1 |
Termination |
Sabit ya da esnek Vida bağlantısı M20 x 1.5 |
Cable section, minimum |
0,25 mm² |
Cable section, maximum |
2,5 mm² |
Tightening torque of Clips |
0,6 Nm |
Mechanical data - Dimensions
Width |
45 mm |
Height |
100 mm |
Depth |
121 mm |
Ambient conditions
Degree of protection of the enclosure |
IP40 |
Degree of protection of the mounting space |
IP54 |
Degree of protection of clips or terminals |
IP20 |
Ambient temperature |
-25 ... +60 °C |
Storage and transport temperature |
-40 ... +85 °C |
Resistance to vibrations |
10 ... 55 Hz, Genlik 0.35 mm |
Restistance to shock |
10 g / 11 ms |
Ambient conditions - Insulation values
Rated impulse withstand voltage Uimp |
4 kV |
Overvoltage category |
III |
Degree of pollution |
2 |
Electrical data
Frequency range |
50 Hz 60 Hz |
Operating voltage |
24 VAC -15 % / +10 % |
Ripple voltage |
10 % |
Rated operating voltage |
24 VAC |
Rated operating voltage |
24 VDC |
Rated AC voltage for controls, 50 Hz, minimum |
20,4 VAC |
Rated control voltage at AC 50 Hz, maximum |
26,4 VAC |
Rated AC voltage for controls, 60 Hz, minimum |
20,4 VAC |
Rated control voltage at AC 60 Hz, maximum |
26,4 VAC |
Rated AC voltage for controls at DC minimum |
20,4 VDC |
Rated control voltage at DC, maximum |
28,8 VDC |
Electrical power consumption |
3,2 W |
Electrical power consumption |
7,1 VA |
Contact resistance, maximum |
0,1 Ω |
Note (Contact resistance) |
yeni durumda |
Drop-out delay in case of power failure, typically |
80 ms |
Drop-out delay in case of emergency, typically |
30 ms |
Drop-out delay in case of "emergency stop", maximum |
36 ms |
Pull-in delay at automatic start, maximum, typically |
250 ms |
Pull-in delay at RESET, typically |
20 ms |
Material of the contacts, electrical |
AgSn0, Ag-Ni, kendi kendini temizler, pozitif hareket |
Electrical data - Digital inputs
Conduction resistance, maximum |
40 Ω |
Electrical data - Electromagnetic compatibility (EMC)
EMC rating |
EMC-Directive |
Status indication
Indicated operating states |
Konum rölesi K2 Konum rölesi K1 Dahili çalışma gerilimi Ui Konum rölesi K3 |
Other data
Note (applications) |
Güvenlik sensörü Koruma sistemi Acil Stop butonu Halatlı acil stop anahtarları Işıklı güvenlik perdesi |
Note
Note (General) |
Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit. |
Wiring example
Note (Wiring diagram) |
The wiring diagram is shown with guard doors closed and in de-energised condition. Relay outputs: Suitable for 2 channel control, for increase in capacity or number of contacts by means of contactors or relays with positive-guided contacts. The control recognises cross-short, cable break and earth leakages in the monitoring circuit. 2 channel control shown for a guard-door monitor with two contacts, of which at least one contact has positive break, with external reset button (R). (H2) = Geri besleme devresi |
Dil filtresi
Veri sayfası
Çalışma Talimatları ile Uygunluk beyanı
TÜV sertifikasyonu
UL Sertifikası
Adobe Reader’ın son sürümünü indirin
Ürün resmi (katalog özel fotoğraf)
Kablo döşeme örneği
Çalışma prensibi
Sembol (teknik standart)
Schmersal India Pvt. Ltd., Plot No - G-7/1, Ranjangaon MIDC, Tal. - Shirur, Dist.- Pune 412 220
Veriler ve ayrıntılar dikkatli bir şekilde kontrol edilmişlerdir. Görüntüler orijinalden farklı olabilir. Daha fazla teknik veri kılavuzda bulunabilir. Teknik değişiklikler ve hatalar olabilir.
Udarbejdet d. 23.03.2025 20:32