schmersal_s_icon.png

CSS 8-180-2P+D-M-L

品番: 101169558

製品タイプの説明:

CSS 8-180-(1)-(2)-(3)


(1)
2P短絡保護 PNP 安全出力 2 回路
2P+D短絡保護 PNP 安全出力及び診断出力 2 回路

(2)
E個别センサーまたはシリーズの末端センサー
Y直列接続
M多機能接続

(3)
Lケーブル
LSTコネクター付きケーブル
STコネクタープラグ
この型式記号に従って組み合わせられる全ての型式が、提供可能あるいは技術的に実現可能ということではありません。
  • Pre-wired cable 7-pole
  • Comfortable diagnostics through sensor LED and electronic signalling output
  • Thermoplastic enclosure
  • Electronic contact-free, coded system
  • Misaligned actuation possible
  • High repeat accuracy of the switching points
  • Max. length of the sensor chain 200 m
  • Early warning when operating near the limit of the sensor's hysteris range
  • Self-monitoring series-wiring of 16 sensors
  • 2 short-circuit proof PNP safety outputs

Ordering data

Product type description

CSS 8-180-2P+D-M-L

Article number (order number)

101169558

EAN (European Article Number)

4030661295992

eCl@ss number, version 12.0

27-27-46-01

eCl@ss number, version 11.0

27-27-24-03

eCl@ss number, version 9.0

27-27-24-03

ETIM number, version 7.0

EC001829

ETIM number, version 6.0

EC001829

Approvals - Standards

Certificates

TÜV

cULus

UKCA

General data

Standards

EN IEC 60947-5-3

EN IEC 61508

Working principle

誘導型

Housing construction form

シリンダー型、ネジ式

Installation conditions (mechanical)

不適切な

Sensor topology

直列配線用センサー

個别センサーまたはシリーズの末端センサー

Housing material

グラスファイバー強化熱可塑性樹脂

Active area

グラスファイバー強化熱可塑性樹脂

Material of the nuts

グラスファイバー強化熱可塑性樹脂

Reaction time, maximum

30 ms

Duration of risk, maximum

30 ms

Gross weight

149 g

General data - Features

Short circuit detection

Yes

Cross-circuit detection

Yes

Safety functions

Yes

Integral system diagnostics, status

Yes

Number of semi-conductor outputs with signaling function

1

Number of fail-safe digital outputs

2

Number of series-wiring of sensors

16

Safety classification

Vorschriften

EN ISO 13849-1

EN IEC 60947-5-3

EN IEC 61508

Performance Level, up to

e

Category

4

PFH value

2.50 x 10⁻⁹ /h

Safety Integrity Level (SIL), suitable for applications in

3

Mission time

20 Year(s)

Mechanical data

Tightening torque of nuts, maximum

3 Nm

Mechanical data - Switching distances

Switch distance, typical

8 mm

Assured switching distance "ON" Sao

7 mm

Assured switching distance "OFF" Sar

10 mm

Note (switching distance)

All switching distances in accordance EN IEC 60947-5-3

Hysteresis (Switching distance), maximum

0.7 mm

Repeat accuracy R

0.2 mm

Mechanical data - Connection technique

Length of cable

1 m

Termination

ケーブル

Wire cross-section

0.25 mm2

Wire cross-section

23 AWG

Mechanical data - Dimensions

ISO thread of the sensor

M18

width across flats

24 BK

Length of sensor

92 mm

Ambient conditions

Degree of protection

IP65

IP67

Ambient temperature

-25 ... +60 °C

Storage and transport temperature

-25 ... +85 °C

Resistance to vibrations

10 ~ 55 Hz, 振幅 1 mm

Restistance to shock

30 g / 11 ms

Protection class

II

Ambient conditions - Insulation values

Rated insulation voltage Ui

32 VDC

Rated impulse withstand voltage Uimp

0.8 kV

Overvoltage category

III

Degree of pollution

3

Electrical data

Operating voltage

24 VDC -15 % / +10 %

No-load supply current I0, typical

50 mA

Rated operating voltage

24 VDC

Operating current

1,000 mA

Switching frequency, approx.

3 Hz

Utilisation category DC-12

24 VDC / 0.05 A

Electrical data - Safety digital outputs

Rated operating current (safety outputs)

500 mA

Output current, (fail-safe output), maximum

0.5 A

Design of control elements

PNP型

Voltage drop Ud, maximum

0.5 V

Leakage current Ir, maximum

0.5 mA

Voltage, Utilisation category DC-12

24 VDC

Current, Utilisation category DC-12

0.5 A

Voltage, Utilisation category DC-13

24 VDC

Current, Utilisation category DC-13

0.5 A

Electrical data - Diagnostic outputs

Rated operating voltage

24 VDC

Design of control elements

p-type

Voltage drop Ud, maximum

4 V

Voltage, Utilisation category DC-12

24 VDC

Current, Utilisation category DC-12

0.05 A

Voltage, Utilisation category DC-13

24 VDC

Current, Utilisation category DC-13

0.05 A

Status indication

Note (LED switching conditions display)

Multi-coloured LED: Green, Red, Yellow

Pin assignment

PIN 1

A1 Ue Brown

PIN 2

X2 safety input 2: White

PIN 3

A2 GND Blue

PIN 4

Y1 Safety output 1 Black

PIN 5

signalling output: Grey

PIN 6

X2 Safety input 2 violet

PIN 7

Y2 Safety output 2 red

Scope of delivery

Scope of delivery

Actuator must be ordered separately.

Scope of delivery of mounting material

ナット M18 x 1 2個

Accessory

Recommendation (actuator)

CST 180-1

CST 180-2

Recommended safety switchgear

PROTECT PSC1

SRB-E-301ST

SRB-E-201LC

Note

Note (General)

Evaluation requirements: dual-channel safety input, suitable for p-type sensors with NO function. The safety-monitoring module must tolerate internal functional tests of the sensors with cyclic switch-off of the sensor outputs for max. 0.25 ms. Short-circuit recognition by the evaluation is not necessary.

言語フィルター

Wiring example (electr. wiring)

Adobe Readerの最新版をダウンロードしてください

Diagram

EU Declaration of Conformity LOG_COM_lo1de01s
Original



K.A. Schmersal GmbH & Co. KG
Möddinghofe 30
42279 Wuppertal
Germany
Internet: www.schmersal.com
Declaration:We hereby certify that the hereafter described components both in their basic design and construction conform to the applicable European Directives.
Name of the component:CSS 8-180
Type:See ordering code
Description of the component:Non-contact safety sensor
Relevant Directives:Machinery Directive2006/42/EC
 EMC-Directive2014/30/EU
 RoHS-Directive2011/65/EU
Applied standards:EN 60947-5-3:2013
EN ISO 14119:2013
EN ISO 13849-1:2015
EN 61508 parts 1-7:2010
Notified body for Type Examination:TÜV Rheinland Industrie Service GmbH
Am Grauen Stein, 51105 Köln
ID n°: 0035
EC-Type Examination Certificate:01/205/5874.00/21
Person authorised for the compilation of the technical documentation:Oliver Wacker
Möddinghofe 30
42279 Wuppertal
Place and date of issue:Wuppertal, November 29, 2021
 GRA_SIG_ksig-y24
 Authorised signature
Philip Schmersal
Managing Director
UK Declaration of Conformity LOG_COM_lo1de01s
Company:K.A. Schmersal GmbH & Co. KG
Möddinghofe 30
42279 Wuppertal
Germany
Internet: www.schmersal.com
Declaration:We hereby, under sole responsibility, certify that the hereafter described components both in their basic design and construction conform to the relevant statutory requirements, regulations and designated standards of the United Kingdom.
Name of the component:CSS 8-180
Type:See ordering code
Description of the component:Non-contact safety sensor
Relevant legislation:Supply of Machinery (Safety) Regulations2008
 Electromagnetic Compatibility Regulations2016
 The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations2012
Designated standards:EN 60947-5-3:2013
EN ISO 14119:2013
EN ISO 13849-1:2015
EN 61508 parts 1-7:2010
Approved body for Type Examination:TÜV Rheinland UK Ltd.
1011 Stratford Road
Solihull, B90 4BN
ID: 2571
Type examination certificate:01/205U/5874.00/23
UK-Importer /
Person authorised for the compilation of the technical documentation:



Schmersal UK Ltd.
Paul Kenney
Unit 1, Sparrowhawk Close
Enigma Business Park
Malvern, Worcestershire, WR14 1GL
Place and date of issue:Wuppertal, February 6, 2023
 GRA_SIG_ksig-y24
 Authorised signature
Philip Schmersal
Managing Director

Schmersal India Pvt. Ltd., Plot No - G-7/1, Ranjangaon MIDC, Tal. - Shirur, Dist.- Pune 412 220

データと詳細は完全にチェックされました。画像は元の画像と異なる場合があります。技術的なデータはマニュアルで見られます。技術的に変更されたり、エラーの可能性があります。

Generated on 2025/06/27 5:28