PROTECT-IE-02-SK
PROTECT-IE-02-SK
Downloads
Typebenaming van het product: PROTECT-IE-(1)-(2) |
(1) | |
02 | 2 verbreekcontacten (NC) |
11 | 1 maakcontact (NO) / 1 verbreekcontact (NC) |
(2) | |
zonder | Veeraansluitklemmen |
SK | Schroefaansluiting, opsteekbaar |
- Input for up to 4 sensors per interface e.g.: magnetic safety switches type BNS, emergency stop devices, interlocking devices and others
- 2 safety contacts
Ordering data
Product type description |
PROTECT-IE-02-SK |
Article number (order number) |
101189096 |
EAN (European Article Number) |
4250116202225 |
eCl@ss number, version 12.0 |
27-37-18-19 |
eCl@ss number, version 11.0 |
27-37-18-19 |
eCl@ss number, version 9.0 |
27-37-18-19 |
ETIM number, version 7.0 |
EC001449 |
ETIM number, version 6.0 |
EC001449 |
Notice |
Discontinued product |
General data
Standards |
EN IEC 62061 EN ISO 13849-1 EN IEC 60947-5-1 EN IEC 60947-5-3 EN IEC 60947-5-5 EN IEC 61508 EN IEC 60204-1 EN IEC 60947-1 |
Climatic stress |
EN 60068-2-78 |
Housing material |
Kunststof, glasvezelversterkte thermoplast, geventileerd |
Gross weight |
140 g |
General data - Features
Electronic Fuse |
Ja |
Wire breakage detection |
Ja |
Cross-circuit detection |
Ja |
Removable Terminals |
Ja |
Automatic reset function |
Ja |
Earth connection detection |
Ja |
Integral system diagnostics, general |
Ja |
Number of auxiliary contacts |
1 |
Number of LEDs |
5 |
Number of normally closed (NC) |
2 |
Number of safety contacts |
2 |
Safety classification |
Vorschriften |
EN IEC 60947-5-1 EN IEC 61508 |
Stop-Category |
0 |
Safety classification - Relay outputs |
Performance Level, up to |
d |
Category |
3 |
Diagnostic Coverage (DC) Level |
60 % |
PFH value |
2,00 x 10⁻⁷ /h |
Notice |
Geldt voor toepassingen tot max. 36.500 schakelcycli/jaar en met max. 60 % contactlast. |
Safety Integrity Level (SIL), suitable for applications in |
2 |
Mission time |
20 Year(s) |
Common Cause Failure (CCF), minimum |
65 |
Mechanical data
Mechanical life, minimum |
10.000.000 Operations |
Mounting |
Snelbevestiging voor DIN-rail volgens DIN EN 60715 |
Mechanical data - Connection technique
Terminal designations |
IEC/EN 60947-1 |
Termination |
Schroefaansluiting, opsteekbaar |
Cable section, minimum |
0,14 mm² |
Cable section, maximum |
1,5 mm² |
Mechanical data - Dimensions
Width |
48 mm |
Height |
126 mm |
Depth |
61 mm |
Ambient conditions
Degree of protection of the enclosure |
IP20 |
Degree of protection of the mounting space |
IP20 |
Degree of protection of clips or terminals |
IP20 |
Ambient temperature |
-25 ... +55 °C |
Storage and transport temperature |
-40 ... +85 °C |
Resistance to vibrations |
10...55 Hz, Amplitude 0,35 mm, ± 15 % |
Restistance to shock |
30 g / 11 ms |
Ambient conditions - Insulation values
Rated impulse withstand voltage Uimp |
0,8 kV |
Overvoltage category |
III |
Degree of pollution |
2 |
Electrical data
Operating voltage |
24 VDC -15 % / +20 % |
Ripple voltage |
10 % |
Rated operating voltage |
24 VDC |
Rated AC voltage for controls at DC minimum |
20,4 VDC |
Rated control voltage at DC, maximum |
28,8 VDC |
Electrical power consumption |
1,7 W |
Input resistance at Ue |
2.900 Ω |
Contact resistance, maximum |
0,1 Ω |
Note (Contact resistance) |
In nieuwe toestand |
Drop-out delay in case of "emergency stop", maximum |
20 ms |
Pull-in delay at automatic start, maximum |
20 ms |
Electrical data - Safe relay outputs
Voltage, Utilisation category DC-13 |
24 VDC |
Current, Utilisation category DC-13 |
2 A |
Switching capacity, minimum |
10 VDC |
Switching capacity, minimum |
10 mA |
Switching capacity, maximum |
24 VAC |
Switching capacity, maximum |
2 A |
Electrical data - Digital inputs
Input signal, HIGH Signal "1" |
19 - 28,8 VDC |
Input signal, LOW Signal "0" |
0 - 1 VDC |
Conduction resistance, maximum |
40 Ω |
Electrical data - Digital Output
Voltage, Utilisation category DC-12 |
24 VDC |
Current, Utilisation category DC-12 |
0,1 A |
Electrical data - Relay outputs (auxiliary contacts)
Switching capacity, maximum |
24 VDC |
Switching capacity, maximum |
0,1 A |
Electrical data - Electromagnetic compatibility (EMC)
EMC rating |
EMC-Richtlijn |
Status indication
Indicated operating states |
Positie relais K2 Positie relais K1 Positie relais K3 Positie relais K3 |
Other data
Note (applications) |
Veiligheidssensor Beschermvoorziening Noodstopknop Noodstop-trekkoordschakelaars |
Taalfilter
Datasheet
Bedieningshandleiding en conformiteitsverklaring
Download de nieuwste versie van Adobe Reader
Foto van het product (individuele catalogusfoto)
Schakelvoorbeeld
Schakelvoorbeeld
103008070 SRB-E-204PE
- Plug-in screw terminals with coding
- Input expander module
- 1 oder 2-channel control
- Monitoring of 4 sensors
- 2 Safety outputs
- 4 Signalling outputs
103009973 SRB-E-204ST
- Plug-in screw terminals with coding
- STOP 0 Function
- Monitoring of 4 sensors
- Start button / Auto-start
- 2 Safety outputs
- 4 Signalling outputs
EU-conformiteitsverklaring | ![]() |
Original | K.A. Schmersal GmbH & Co. KG Möddinghofe 30 42279 Wuppertal Germany Internet: www.schmersal.com |
Verklaring: | Hiermee verklaren wij dat de hieronder beschreven producten op grond van hun ontwerp en constructie beantwoorden aan de relevante Europese Richtlijnen. |
Benaming van de component: | PROTECT-IE |
Type: | zie bestelsleutel |
Beschrijving van de component: | Veiligheidsmodule als ingangsuitbreidingsmodule in combinatie met een veiligheidsmodule als basistoestel |
Geharmoniseerde Richtlijnen: | Machinerichtlijn | 2006/42/EG |
EMC-Richtlijn | 2014/30/EU | |
RoHS-Richtlijn | 2011/65/EU |
Toegepaste normen: | EN 60947-5-1:2004 + AC:2005 + A1:2009 EN 60947-5-1:2017 + AC:2020 EN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 61326-3-1:2017 |
Erkende instantie voor het certificeren van het QS systeem volgens Bijlage X, 2006/42/EG: | TÜV Rheinland Industrie Service GmbH Am Grauen Stein, 51105 Köln Kenn Nr.: 0035 |
Gemachtigde voor het samenstellen van de technische documentatie: | Oliver Wacker Möddinghofe 30 42279 Wuppertal |
Plaats en datum van opstelling: | Wuppertal, 21 maart 2023 |
![]() |
Rechtsgeldige handtekening Philip Schmersal Directeur |
UK Declaration of Conformity | ![]() |
Company: | K.A. Schmersal GmbH & Co. KG Möddinghofe 30 42279 Wuppertal Germany Internet: www.schmersal.com |
Declaration: | We hereby, under sole responsibility, certify that the hereafter described components both in their basic design and construction conform to the relevant statutory requirements, regulations and designated standards of the United Kingdom. |
Name of the component: | PROTECT-IE |
Type: | See ordering code |
Description of the component: | Safety-monitoring module as input expander in conjunction with a safety-monitoring module as basic device |
Relevant legislation: | Supply of Machinery (Safety) Regulations | 2008 |
Electromagnetic Compatibility Regulations | 2016 | |
The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations | 2012 |
Designated standards: | EN 60947-5-1:2004 + AC:2005 + A1:2009 EN 60947-5-1:2017 + AC:2020 EN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 61326-3-1:2017 |
Notified body, which approved the full quality assurance system, referred to in Appendix X, 2006/42/EC: | TÜV Rheinland Industrie Service GmbH Am Grauen Stein 51105 Köln ID n°: 0035 |
UK-Importer / Person authorised for the compilation of the technical documentation: | Schmersal UK Ltd. Paul Kenney Unit 1, Sparrowhawk Close Enigma Business Park Malvern, Worcestershire, WR14 1GL |
Place and date of issue: | Wuppertal, March 21, 2023 |
![]() |
Authorised signature Philip Schmersal Managing Director |
Schmersal India Pvt. Ltd., Plot No - G-7/1, Ranjangaon MIDC, Tal. - Shirur, Dist.- Pune 412 220
De genoemde gegevens en informatie zijn zorgvuldig gecontroleerd. Afbeeldingen kunnen afwijken van het origineel. Verdere technische gegevens zijn te vinden in de handleiding. Technische wijzigingen en fouten voorbehouden.