schmersal_s_icon.png

AES 1136-2185

Numer katalogowy: 101172221

Downloads

TraceParts Dane CAD
ePLAN Dane
CADENAS Dane CAD
  • Monitoring of BNS range magnetic safety sensors
  • 1 safety contact, STOP 0
  • 2 Signalling outputs

Ordering data

Note (Delivery capacity)

Niedostępne!

Product type description

AES 1136-2185

Article number (order number)

101172221

EAN (European Article Number)

4030661300450

eCl@ss number, version 12.0

27-37-18-19

eCl@ss number, version 11.0

27-37-18-19

eCl@ss number, version 9.0

27-37-18-19

ETIM number, version 7.0

EC001449

ETIM number, version 6.0

EC001449

Notice

Discontinued product

Approvals - Standards

Certificates

cULus

General data

Standards

BG-GS-ET-14

BG-GS-ET-20

EN IEC 62061

EN ISO 13849-1

EN IEC 60947-5-1

EN IEC 60947-5-3

EN IEC 60947-5-5

EN IEC 60204-1

EN IEC 60947-1

Climatic stress

EN 60068-2-3

BG-GS-ET-14

Housing material

Tworzywo, Tworzywo termoplastyczne wzmocnione włóknem szklanym, obudowa wentylowana

Gross weight

190 g

General data - Features

Wire breakage detection

Tak

Cross-circuit detection

Tak

Automatic reset function

Tak

Start-up test

Tak

Earth connection detection

Tak

Integral system diagnostics, status

Tak

Number of LEDs

1

Number of normally closed (NC)

2

Number of normally open (NO)

1

Number of undelayed semi-conductor outputs with signaling function

2

Number of safety contacts

1

Number of signalling outputs

2

Safety classification

Vorschriften

EN ISO 13849-1

EN IEC 61508

Stop-Category

0

Safety classification - Relay outputs

Performance Level, up to

d

Category

3

PFH value

1,00 x 10⁻⁷ /h

Safety Integrity Level (SIL), suitable for applications in

2

Mission time

20 Year(s)

Mechanical data

Mechanical lifetime, minimum

20.000.000 Operations

Mounting

montaż na standardowej szynie DIN wg EN 60715

Mechanical data - Connection technique

Terminal designations

IEC/EN 60947-1

Cable section, minimum

0,25 mm²

Cable section, maximum

2,5 mm²

Tightening torque of Clips

0,6 Nm

Allowed type of cable

solid single-wire

flexible

Terminal (mechanical)

1000075113

Mechanical data - Dimensions

Width

22,5 mm

Height

100 mm

Depth

121 mm

Ambient conditions

Degree of protection of the enclosure

IP40

Degree of protection of the installation space

IP54

Degree of protection of clips or terminals

IP20

Ambient temperature

+0 ... +55 °C

Storage and transport temperature

-25 ... +70 °C

Resistance to vibrations

10...55 Hz, amplituda 0,35 mm, ± 15 %

Restistance to shock

30 g / 11 ms

Ambient conditions - Insulation values

Rated impulse withstand voltage Uimp

4 kV

Overvoltage category

III

Degree of pollution

2

Electrical data

Frequency range

50 Hz

60 Hz

Operating voltage

24 VAC -15 % / +10 %
24 VDC -10 % / +20 %

Ripple voltage

10 %

Thermal test current

6 A

Rated operating voltage

24 VAC

Rated operating voltage

24 VDC

Rated AC voltage for controls, 50 Hz, minimum

20.4 VAC

Rated control voltage at AC 50 Hz, maximum

26.4 VAC

Rated AC voltage for controls, 60 Hz, minimum

20.4 VAC

Rated control voltage at AC 60 Hz, maximum

26.4 VAC

Rated AC voltage for controls at DC minimum

20,4 VDC

Rated control voltage at DC, maximum

28,8 VDC

Electrical power consumption

5 W

Contact resistance, maximum

0,1 Ω

Note (Contact resistance)

w nowym stanie

Drop-out delay in case of power failure, typically

80 ms

Drop-out delay in case of emergency, typically

20 ms

Pull-in delay at automatic start, maximum, typically

100 ms

Pull-in delay at RESET, typically

20 ms

Material of the contacts, electrical

Ag-Ni 10 pozłacane 0,2 µm

Electrical data - Safe relay outputs

Voltage, Utilisation category AC-15

230 VAC

Current, Utilisation category AC-15

6 A

Voltage, Utilisation category DC-13

24 VDC

Current, Utilisation category DC-13

6 A

Switching capacity, minimum

10 VDC

Switching capacity, minimum

10 mA

Switching capacity, maximum

250 VAC

Switching capacity, maximum

8 A

Electrical data - Digital inputs

Input signal, HIGH Signal "1"

10 … 30 VDC

Input signal, LOW Signal "0"

0 … 2 VDC

Conduction resistance, maximum

40 Ω

Electrical data - Digital Output

Voltage, Utilisation category DC-12

24 VDC

Current, Utilisation category DC-12

0,1 A

Electrical data - Relay outputs (auxiliary contacts)

Switching capacity, maximum

24 VDC

Switching capacity, maximum

2 A

Electrical data - Electromagnetic compatibility (EMC)

EMC rating

Dyrektywa o kompatybilności elektromagnetycznej

Integral system diagnosis (ISD)

Note (ISD -Faults)

Następujące błędy zostały zarejestrowane przez moduły bezpieczeństwa i wskazane przez ISD.

Faults

Błąd załączenia lub wyłączenia przekaźnika bezpieczeństwa

Niepowodzenie otwarcia lub zamknięcia kontaktów drzwiowych

Monitorowanie zwarć międzykanałowych lub zwarcia połączeń wyłącznika

Przerwanie połączeń wyłączników

Niezadziałanie obwodów wejściowych lub obwodów przekaźnikowych sterowania modułu monitorującego bezpieczeństwa

Other data

Note (applications)

Czujnik bezpieczeństwa

Osłony bezpieczeństwa

Note

Note (General)

Obciążenia indukcyjne (np. styczniki, przekaźniki itp.) należy wytłumić przy pomocy odpowiedniego obwodu.

Wiring example

Note (Wiring diagram)

Schemat okablowania dla zamknietej osłony bezpieczeńatwa i stanu z wyłączonym zasilaniem.

Do zabezpieczenia osłony bezpieczeństwa, PL do d i Kategoria 3

Monitorowanie 1 osłony, wyposażonej w magnetyczny czujnik bezpieczeństwa typoszeregu BNS

Jeżeli do przełączania obciążenia używany jest jeden lub dwa przekaźniki lub styczniki zewnętrzne, system może być sklasyfikowany jedynie w kategorii 3 wg EN ISO 13849-1, jeżeli wykluczenie błędu "awaria styczników zewnętrznych" może zostać udowodnione i udokumentowane, np. przez zastosowanie niezawodnych styczników o mniejszych wartościach znamionowych. Drugi stycznik prowadzi do zwiększenia bezpieczeństwa przez redundancję wyłączania obciążenia.

Modyfikacja dla dwóch zestyków NC: Moduł bezpieczeństwa można zmodyfikować tak, aby monitorował dwa zestyki NC poprzez zmostkowanie przyłączy A1 i X1 Przy takiej konfiguracji detekcja zwarcia skrośnego przestaje działać.

Przedłużenie opóźnienia aktywacji: Opóźnienie aktywacji może być zwiększane od 0,1 s do 1,0 s poprzez zmianę pozycji zworki umieszczonej pod pokrywą urządzenia.

Tabele ISD (Zintegrowanego Systemu Diagnostyczego) dla analizy wskazań błędów i ich przyczyn zamieszczono w załączniku.

Filtr językowy

Przykład połączeń (okablowanie elektryczne)

pobierz najnowszą wersję Adobe Reader

103009970 SRB-E-201LC
  • Plug-in screw terminals with coding
  • STOP 0 Function
  • 1 oder 2-channel control
  • Start button / Auto-start
  • 2 Safety outputs 2 A
  • 1 Signalling output

103007672 SRB-E-301ST
  • Plug-in screw terminals with coding
  • STOP 0 Function
  • 1 oder 2-channel control
  • Start button / Auto-start
  • 1 Auxiliary contact
  • 3 safety contacts


Schmersal India Pvt. Ltd., Plot No - G-7/1, Ranjangaon MIDC, Tal. - Shirur, Dist.- Pune 412 220

Dane zostały starannie sprawdzone. Zdjęcia mogą odbiegać od rzeczywistości. Dalsze dane techniczne znajdują się w instrukcji obsługi. Możliwe są zmiany i błędy techniczne.