SRB301X4-115V
SRB301X4-115V
Downloads
- Suitable for the signal processing of outputs with contact sensors
- Suitable for signal processing of outputs connected to potentials (AOPDs), e.g. safety light grids/curtains
- 3 safety contacts, STOP 0
- 1 Signalling output
Ordering data
Note (Delivery capacity) |
Niedostępne! |
Replacement article number |
101188431 |
Product type description |
SRB301X4-115V |
Article number (order number) |
101183212 |
EAN (European Article Number) |
4250116202164 |
eCl@ss number, version 12.0 |
27-37-18-19 |
eCl@ss number, version 11.0 |
27-37-18-19 |
eCl@ss number, version 9.0 |
27-37-18-19 |
ETIM number, version 7.0 |
EC001449 |
ETIM number, version 6.0 |
EC001449 |
Approvals - Standards
Certificates |
cULus |
General data
Standards |
EN IEC 62061 EN ISO 13849-1 EN IEC 60947-5-1 EN IEC 60947-5-3 EN IEC 60947-5-5 EN IEC 61508 EN IEC 60204-1 EN IEC 60947-1 |
Climatic stress |
EN 60068-2-78 |
Housing material |
Tworzywo, Tworzywo termoplastyczne wzmocnione włóknem szklanym, obudowa wentylowana |
Gross weight |
450 g |
General data - Features
Electronic Fuse |
Tak |
Wire breakage detection |
Tak |
Cross-circuit detection |
Tak |
Start input |
Tak |
Feedback circuit |
Tak |
Automatic reset function |
Tak |
Earth connection detection |
Tak |
Integral system diagnostics, status |
Tak |
Number of auxiliary contacts |
1 |
Number of LEDs |
3 |
Number of normally closed (NC) |
2 |
Number of safety contacts |
3 |
Safety classification |
Vorschriften |
EN IEC 60947-5-1 EN IEC 61508 |
Stop-Category |
0 |
Safety classification - Relay outputs |
Performance Level, up to |
e |
Category |
4 |
Diagnostic Coverage (DC) Level |
> 99 % |
PFH value |
2,00 x 10⁻⁸ /h |
Safety Integrity Level (SIL), suitable for applications in |
3 |
Mission time |
20 Year(s) |
Common Cause Failure (CCF), minimum |
65 |
Mechanical data
Mechanical life, minimum |
10 000 000 Operations |
Mounting |
montaż na standardowej szynie DIN wg EN 60715 |
Mechanical data - Connection technique
Terminal designations |
IEC/EN 60947-1 |
Termination |
sztywny lub elastyczny Połączenie śrubowe M20 x 1.5 |
Cable section, minimum |
0,25 mm² |
Cable section, maximum |
2,5 mm² |
Tightening torque of Clips |
0,6 Nm |
Mechanical data - Dimensions
Width |
45 mm |
Height |
100 mm |
Depth |
121 mm |
Ambient conditions
Degree of protection of the enclosure |
IP40 |
Degree of protection of the mounting space |
IP54 |
Degree of protection of clips or terminals |
IP20 |
Ambient temperature |
-25 ... +60 °C |
Storage and transport temperature |
-40 ... +85 °C |
Resistance to vibrations |
10 ... 55 Hz, amplituda 0,35 mm |
Restistance to shock |
30 g / 11 ms |
Ambient conditions - Insulation values
Rated impulse withstand voltage Uimp |
4 kV |
Overvoltage category |
III |
Degree of pollution |
2 |
Electrical data
Frequency range |
50 Hz 60 Hz |
Operating voltage |
115 VAC -15 % / +10 % |
Rated operating voltage |
115 VAC |
Rated AC voltage for controls, 50 Hz, minimum |
97,8 VAC |
Rated control voltage at AC 50 Hz, maximum |
126,5 VAC |
Rated AC voltage for controls, 60 Hz, minimum |
97,8 VAC |
Rated control voltage at AC 60 Hz, maximum |
126,5 VAC |
Utilisation category AC-15 |
230 VAC |
Utilisation category AC-15 |
6 A |
Utilisation category DC-13 |
24 VDC |
Utilisation category DC-13 |
6 A |
Electrical power consumption |
2 W |
Electrical power consumption |
4,6 VA |
Contact resistance, maximum |
0,1 Ω |
Note (Contact resistance) |
w nowym stanie |
Drop-out delay in case of power failure, typically |
40 ms |
Drop-out delay in case of "emergency stop", maximum |
20 ms |
Pull-in delay at RESET, typically |
20 ms |
Material of the contacts, electrical |
AgSn0. samoczyszczący, wymuszone prowadzenie |
Electrical data - Digital inputs
Conduction resistance, maximum |
40 Ω |
Electrical data - Electromagnetic compatibility (EMC)
EMC rating |
Dyrektywa o kompatybilności elektromagnetycznej |
Status indication
Indicated operating states |
Przekaźnik pozycyjny K2 Przekaźnik pozycyjny K1 |
Other data
Note (applications) |
Osłony bezpieczeństwa Przycisk stopu awaryjnego Linkowe wyłączniki stopu awaryjnego Bariery świetlne bezpieczeństwa |
Note
Note (General) |
Obciążenia indukcyjne (np. styczniki, przekaźniki itp.) należy wytłumić przy pomocy odpowiedniego obwodu. |
Wiring example
Note (Wiring diagram) |
Schemat okablowania dla zamknietej osłony bezpieczeńatwa i stanu z wyłączonym zasilaniem. Wyjścia przekaźnikowe: odpowiednie dla sterowania 2-kanałowego, dla zwiększenia pojemności lub liczby zestyków za pomocą styczników lub przekaźników o zestykach lustrzanych. Sterownik rozpoznaje zwarcie międzykanałowe, przerwanie kabla lub upływ doziemny w obwodzie monitorowania. Pokazano sterowanie 2-kanałowe dla monitorowania osłony bezpieczeństwa z dwoma zestykami, z których przynajmniej jeden zestyk jest zestykiem z wymuszonym rozwarciem, z zewnętrznym przyciskiem resetu (R). (H2) = Obwód sprzężenia zwrotnego |
Filtr językowy
Karta katalogowa
Instrukcja obsługi i deklaracja zgodności
Certyfikat UL
Przykład połączeń (okablowanie elektryczne)
pobierz najnowszą wersję Adobe Reader
Zdjęcie produktu (pojedyncze zdjęcie katalogowe)
Przykład okablowania
Symbol (norma techniczna)
Schmersal India Pvt. Ltd., Plot No - G-7/1, Ranjangaon MIDC, Tal. - Shirur, Dist.- Pune 412 220
Dane zostały starannie sprawdzone. Zdjęcia mogą odbiegać od rzeczywistości. Dalsze dane techniczne znajdują się w instrukcji obsługi. Możliwe są zmiany i błędy techniczne.
Wygenerowano dnia 08.04.2025, 23:22