- UNIVERSAL Gateway for the series-wiring of the diagnostic signals of safety
switchgear with integrated SD interface. - Comprehensive volumes of status and diagnostic data of the SD devices are transmitted to the control system through the field bus interface.
- Series-wiring of the diagnostic lines of max. 31 safety switchgear
- Series-wiring of different devices possible
- Reduced wiring efforts and costs as a result of the series-wiring of the safety channels and the diagnostic cables in the field.
- Automatic addressing of the safety switchgear in the SD interface
Ordering data
Product type description |
SD-I-U-CCL |
Article number (order number) |
101209435 |
EAN (European Article Number) |
4030661448879 |
eCl@ss number, version 12.0 |
27-23-02-06 |
eCl@ss number, version 11.0 |
27-23-02-06 |
eCl@ss number, version 9.0 |
27-23-02-08 |
ETIM number, version 7.0 |
EC001099 |
ETIM number, version 6.0 |
EC001099 |
Approvals - Standards
Certificates |
cULus |
General data
Gross weight |
200 g |
General data - Features
Integral system diagnostics, status |
Oui |
Number of LEDs |
1 |
Mechanical data
Mounting |
Fixation rapide sur rails DIN standards selon DIN EN 60715 |
Mechanical data - Connection technique
Termination |
Bornes à ressort |
Mechanical data - Dimensions
Width |
50 mm |
Height |
100 mm |
Depth |
80 mm |
Ambient conditions
Degree of protection of the enclosure |
IP20 |
Ambient temperature |
+0 ... +55 °C |
Storage and transport temperature |
-25 ... +75 °C |
Relative humidity, minimum |
30 % |
Relative humidity, maximum |
85 % |
Note (Relative humidity) |
sans condensation |
Resistance to vibrations |
10 ... 57 Hz, amplitude 0,35 mm 57 ... 150 Hz, avec 5 g |
Restistance to shock |
10 g |
Ambient conditions - Insulation values
Rated insulation voltage Ui |
32 V |
Rated impulse withstand voltage Uimp |
0,5 kV |
Overvoltage category |
II |
Degree of pollution |
2 |
Electrical data
Operating voltage |
24 VDC -15 % / +20 % |
Rated operating voltage |
24 VDC |
Operating current |
500 mA |
Electrical data - Communication protocols
Feldbus Protokoll |
CC-Link |
Electrical data - Electromagnetic compatibility (EMC)
Electromagnetic compatibility |
EN 61000-4-2 EN 61000-4-4 EN 61000-4-5 |
Interfering radiation |
IEC 61000-6-4 (2002) |
EMC rating |
EN 61000-4-3 EN 61000-4-6 |
Other data
Note (applications) |
Capteur de sécurité Dispositif de protection |
Filtre de langue
Fiches techniques
Mode d'emploi et déclaration de conformité
Certificat UL
Fiche technique (PDF provisoire)
Fiches descriptives des appareils
Télécharger la dernière version d'Adobe Reader
Photo du produit (photo individuelle de catalogue)
Exemple de câblage
Application Note
ID: p-sd-i-u-ccl
Video ID: SD-Interface-Mr-Safety
Déclaration UE de conformité | ![]() |
Original | K.A. Schmersal GmbH & Co. KG Möddinghofe 30 42279 Wuppertal Germany Internet: www.schmersal.com |
Déclaration: | Par la présente, nous certifions que les composants identifiés ci-après répondent de par leur conception et leur construction aux exigences des Directives Européennes applicables. |
Désignation du composant | SD-I-U-… |
Type: | voir exemple de commande |
Description du composant: | Passerelle universelle pour diagnostic en série (SD-I-U-..) |
Directives pertinentes: | Directive CEM | 2014/30/EU |
Directive RoHS | 2011/65/EU |
Normes appliquées: | DIN EN 61000-6-2:2006 DIN EN 61000-6-4:2011 EN 61326-3-1:2008 |
Représentant autorisé à préparer et composer la documentation technique: | Oliver Wacker Möddinghofe 30 42279 Wuppertal |
Lieu et date de l'émission: | Wuppertal, le 12 novembre 2018 |
![]() |