SRB400CA/Q 24VDC
SRB400CA/Q 24VDC
Downloads
- Level 1: Reset without edge detection, Optional Automatic reset function, Short-circuit recognition, Level 2: / Opener (NC) Normally open contact (NO)
- Two-functions safety monitoring module (double evaluation)
- 2 x 2 enabling paths with different shut-down behaviour, e.g. emergency exit opens both enabling paths (level 1); guard door monitoring only opens the second enabling path (level 2)
- Suitable for signal processing of potential-free contacts, e.g. Emergency Stop command devices (level 1), position switches with safety function, solenoid interlocks and safety sensors (level 2)
Ordering data
Replacement article number |
101177157 |
Product type description |
SRB400CA/Q 24VDC |
Article number (order number) |
101176213 |
EAN (European Article Number) |
4250116202010 |
eCl@ss number, version 12.0 |
27-37-18-19 |
eCl@ss number, version 11.0 |
27-37-18-19 |
eCl@ss number, version 9.0 |
27-37-18-19 |
ETIM number, version 7.0 |
EC001449 |
ETIM number, version 6.0 |
EC001449 |
Notice |
Discontinued product |
Approvals - Standards
Certificates |
cULus |
General data
Standards |
EN IEC 62061 EN ISO 13849-1 EN IEC 60947-5-1 EN IEC 60947-5-3 EN IEC 60947-5-5 EN IEC 61508 EN IEC 60204-1 EN IEC 60947-1 |
Climatic stress |
EN 60068-2-78 |
Housing material |
materiale sintetico, termoplastica rinforzata con fibra di vetro, ventilata |
Gross weight |
235 g |
General data - Features
Electronic Fuse |
Sì |
Wire breakage detection |
Sì |
Cross-circuit detection |
Sì |
Removable Terminals |
Sì |
Start input |
Sì |
Feedback circuit |
Sì |
Automatic reset function |
Sì |
Earth connection detection |
Sì |
Integral system diagnostics, status |
Sì |
Number of inputs for NC |
3 |
Number of inputs for NO |
1 |
Number of LEDs |
6 |
Number of safety contacts |
4 |
Safety classification |
Vorschriften |
EN IEC 60947-5-1 EN IEC 61508 |
Stop-Category |
0 |
Safety classification - Relay outputs |
Performance Level, stop 0, up to |
e |
Category, Stop 0 |
4 |
Diagnostic Coverage (DC) Level, Stop 0 |
≥ 99 % |
PFH value, Stop 0 |
2,00 x 10⁻⁸ /h |
Safety Integrity Level (SIL), Stop 0, suitable for applications in |
3 |
Mission time |
20 Year(s) |
Common Cause Failure (CCF), minimum |
65 |
Mechanical data
Mechanical life, minimum |
10.000.000 Operations |
Mounting |
fissaggio rapido per guide DIN secondo DIN EN 60715 |
Mechanical data - Connection technique
Terminal designations |
IEC/EN 60947-1 |
Termination |
rigido o flessibile Collegamento a vite M20 x 1.5 |
Cable section, minimum |
0,25 mm² |
Cable section, maximum |
2,5 mm² |
Tightening torque of Clips |
0,6 Nm |
Mechanical data - Dimensions
Width |
22,5 mm |
Height |
100 mm |
Depth |
121 mm |
Ambient conditions
Degree of protection of the enclosure |
IP40 |
Degree of protection of the mounting space |
IP54 |
Degree of protection of clips or terminals |
IP20 |
Ambient temperature |
-25 ... +45 °C |
Storage and transport temperature |
-40 ... +85 °C |
Resistance to vibrations |
10 ... 55 Hz, ampiezza 0,35 mm |
Restistance to shock |
10 g / 11 ms |
Ambient conditions - Insulation values
Rated impulse withstand voltage Uimp |
4 kV |
Overvoltage category |
III |
Degree of pollution |
2 |
Electrical data
Operating voltage |
24 VDC -10 % / +20 % |
Ripple voltage |
10 % |
Rated operating voltage |
24 VDC |
Rated AC voltage for controls at DC minimum |
20,4 VDC |
Rated control voltage at DC, maximum |
28,8 VDC |
Electrical power consumption |
4,4 W |
Contact resistance, maximum |
0,1 Ω |
Note (Contact resistance) |
in perfette condizioni |
Drop-out delay in case of power failure, typically |
80 ms |
Drop-out delay in case of emergency, typically |
20 ms |
Pull-in delay at automatic start, maximum, typically |
100 ms |
ON delay at automatic start |
Regolabile |
Pull-in delay at RESET, typically |
20 ms |
Material of the contacts, electrical |
Ag-Ni, autopulente, azione obbligata |
Electrical data - Safe relay outputs
Voltage, Utilisation category AC-15 |
250 VAC |
Current, Utilisation category AC-15 |
6 A |
Voltage, Utilisation category DC-13 |
24 VDC |
Current, Utilisation category DC-13 |
6 A |
Switching capacity, minimum |
10 VDC |
Switching capacity, minimum |
10 mA |
Switching capacity, maximum |
250 VAC |
Switching capacity, maximum |
8 A |
Electrical data - Digital inputs
Conduction resistance, maximum |
40 Ω |
Electrical data - Relay outputs (auxiliary contacts)
Switching capacity, maximum |
24 VDC |
Switching capacity, maximum |
2 A |
Electrical data - Electromagnetic compatibility (EMC)
EMC rating |
Direttiva EMC |
Status indication
Indicated operating states |
posizione dei relè K2 posizione dei relè K1 tensione d'esercizio interna Ui posizione dei relè K3 |
Other data
Note (applications) |
Sensore di sicurezza Dispositivo di protezione Pulsante di arresto d'emergenza Interruttori a fune d'emergenza |
Note
Note (General) |
Soppresori induttivi (contattore, relè ecc.) vanno ripristinati con una commutazione idonea. |
Note (Cross-circuit detection) |
Livello 1 |
Wiring example
Note (Wiring diagram) |
L'esempio di commutazione è rappresentato con dispositivi di sicurezza chiusi e in condizione senza tensione. Livello di performance: azionamento 2 canale, adatto per il rafforzamento, quindi la duplicazione, dei contatti mediante contattori, oppure relè con contatti ad azione obbligata. Il controllo riconosce cortocircuiti trasversali, rotture di cavo e dispersioni verso terra nel circuito sorvegliato. Livello di ingresso: circuito di comando bicanale, rappresentato con l'esempio di un circuito d'emergenza (livello 1) con un pulsante di reset esterno (R), ed un controllo di una porta di sicurezza (livello 2) con circuito di ritorno (H2). Avvio automatico: (Livello 1) La programmazione dell'avvio automatico avviene mediante integrazione del circuito di ripristino ai morsetti X1 / +24VDC. Avvio automatico: (Livello 2) La programmazione dell'avvio automatico avviene mediante integrazione del circuito di ripristino ai morsetti X2 / +24VDC. Se il circuito di ripristino non è richiesto, sostituirlo con un ponticello. |
Filtro lingua
Scheda Tecnica
Manuale d'istruzioni e dichiarazione UE di conformità
Certificazione UL
Esempio di collegamento (cablaggio elettrico)
Download dell'ultima versione di Adobe Reader
Immagine del prodotto (foto singola per catalogo)
Esempio di azionamento
Esempio di azionamento
Simbolo (standard tecnico)
103007221 SRB-E-402ST
- Two-functions safety monitoring module (double evaluation), 2 x STOP 0
- 2 x 1 oder 2-channel control
- 2 x Start button / Auto-start
- 1 x Monitoring two-hand control panels to ISO 13851
- 2 safety contacts
- 2 Safety outputs
Schmersal India Pvt. Ltd., Plot No - G-7/1, Ranjangaon MIDC, Tal. - Shirur, Dist.- Pune 412 220
I dettagli e i dati qui riportati sono stati attentamente verificati. Le immagini possono differire dagli originali. Altri dati tecnici possono essere trovati nei manuali. Salvo modifiche tecniche o errori.
Generato il 15/04/2025, 19:02