schmersal_s_icon.png

AES 6112

Artikelnummer: 101112461

Downloads

TraceParts CAD-Daten
ePLAN Daten
CADENAS CAD-Daten
SISTEMA Daten
  • HINWEIS: Nicht mehr lieferbar! (Ersatz: AES 1112)
  • Überwachung von magnetischen Sicherheits-Sensoren der Reihe BNS
  • 1 Sicherheitskontakt, STOP 0

Bestelldaten

Note (Delivery capacity)

Nicht mehr lieferbar!

Product type description

AES 6112

Article number (order number)

101112461

EAN (European Article Number)

4030661058443

eCl@ss number, version 12.0

27-37-18-19

eCl@ss number, version 11.0

27-37-18-19

eCl@ss number, version 9.0

27-37-18-19

ETIM number, version 7.0

EC001449

ETIM number, version 6.0

EC001449

Zulassungen - Vorschriften

Certificates

cULus

Allgemeine Daten

Standards

BG-GS-ET-14

BG-GS-ET-20

EN IEC 62061

EN ISO 13849-1

EN IEC 60947-5-1

EN IEC 60947-5-3

EN IEC 60947-5-5

EN IEC 60204-1

EN IEC 60947-1

Housing material

Kunststoff, glasfaserverstärkter Thermoplast

Gross weight

125 g

Allgemeine Daten - Eigenschaften

Wire breakage detection

Ja

Cross-circuit detection

Ja

Automatic reset function

Ja

Reset after disconnection of supply voltage

Ja

Integral system diagnostics, status

Ja

Number of LEDs

1

Number of normally closed (NC)

4

Number of normally open (NO)

2

Number of safety contacts

1

Sicherheitsbetrachtung

Vorschriften

EN ISO 13849-1

EN IEC 61508

Stop-Category

0

Sicherheitsbetrachtung - Relaisausgänge

Performance Level, up to

d

Category

3

PFH value

1,00 x 10⁻⁷ /h

Notice

bis max. 50.000 Schaltzyklen/Jahr und bei max. 80% Kontaktlast

Safety Integrity Level (SIL), suitable for applications in

2

Mission time

20 Year(s)

Mechanische Daten

Mechanical lifetime, minimum

50.000.000 Operations

Mounting

Schnellbefestigung für Normschiene nach DIN EN 60715

Mechanische Daten - Anschlusstechnik

Termination

starr oder flexibel

Schraubanschluss M20 x 1.5

Cable section, maximum

1,5 mm²

Mechanische Daten - Abmessungen

Width

48 mm

Height

96 mm

Depth

58 mm

Umgebungsbedingungen

Degree of protection of the enclosure

IP40

Degree of protection of the installation space

IP54

Degree of protection of clips or terminals

IP20

Ambient temperature

+0 ... +55 °C

Storage and transport temperature

-25 ... +70 °C

Resistance to vibrations

10 ... 55 Hz, Amplitude 0,35 mm, ± 15 %

Restistance to shock

30 g / 11 ms

Umgebungsbedingungen - Isolationskennwerte

Rated impulse withstand voltage Uimp

4,8 kV

Overvoltage category

III

Degree of pollution

2

Elektrische Daten

Frequency range

50 Hz

60 Hz

Operating voltage

24 VDC -15 % / +15 %

Thermal test current

5 A

Rated operating voltage

24 VDC

Operating current

100 mA

Rated AC voltage for controls, 50 Hz, minimum

20.4

Rated control voltage at AC 50 Hz, maximum

26.4

Rated AC voltage for controls, 60 Hz, minimum

20.4

Rated control voltage at AC 60 Hz, maximum

26.4

Rated AC voltage for controls at DC minimum

20,4 VDC

Rated control voltage at DC, maximum

27,6 VDC

Electrical power consumption

2,5 W

Contact resistance, maximum

0,1 Ω

Note (Contact resistance)

in Neuzustand

Drop-out delay in case of power failure, typically

80 ms

Drop-out delay in case of emergency, typically

20 ms

Pull-in delay at automatic start, maximum, typically

100 ms

Pull-in delay at RESET, typically

20 ms

Material of the contacts, electrical

AgCdO

Elektrische Daten - Sichere Relaisausgänge

Voltage, Utilisation category AC-15

230 VAC

Current, Utilisation category AC-15

6 A

Voltage, Utilisation category DC-13

24 VDC

Current, Utilisation category DC-13

6 A

Switching capacity, minimum

10 VDC

Switching capacity, minimum

10 mA

Switching capacity, maximum

250 VAC

Switching capacity, maximum

8 A

Elektrische Daten - Digitale Eingänge

Conduction resistance, maximum

40 Ω

Elektrische Daten - Relaisausgänge (Hilfskontakte)

Switching capacity, maximum

24 VDC

Switching capacity, maximum

2 A

Elektrische Daten - Elektromagnetische Verträglichkeit (EMV)

EMC rating

EN 61000-4-3

EN 61000-4-6

IEC 61000-6-2

Zustandsanzeige

Indicated operating states

Freigabe

Sonstige Daten

Note (applications)

Sicherheits-Sensor

Schutzeinrichtung

Hinweis

Note (General)

Induktive Verbraucher (Schütze, Relais etc.) sind durch eine geeignete Beschaltung zu entstören.

Schaltungsbeispiel

Note (Wiring diagram)

Zur Absicherung von einer oder mehreren Schutzeinrichtungen bis zu PL c und Kategorie 1

Überwachung mehrerer Schutzeinrichtungen mit magnetischen Sicherheits-Sensoren der Reihe BNS

Das Schaltungsbeispiel ist bei geschlossenen Schutzeinrichtungen und im spannungslosen Zustand dargestellt.

Überwachung von weiteren Schutzeinrichtungen: An S2 können analog zu S1 weitere magnetische Sicherheits-Sensoren angeschlossen werden.

101128982 AES 1112 24 VDC
  • Überwachung von magnetischen Sicherheits-Sensoren der Reihe BNS
  • 1 Sicherheitskontakt, STOP 0


Schmersal, Inc., 115 E Stevens Ave, Suite 208, Valhalla, NY 10595

Die genannten Daten und Angaben wurden sorgfältig geprüft. Abbildungen können vom Original abweichen. Weitere technische Daten finden Sie in der Betriebsanleitung. Technische Änderungen und Irrtümer vorbehalten.

Generiert am: 13.08.2025, 08:04