schmersal_s_icon.png

CSP 11-34F2-D-M-ST

项目编号: 101208005

下载

追踪备件 CAD数据
计划 数据
CADENAS CAD数据
  • 1 x connector plug M12, 8-pole
  • Actuation from side
  • with On-site acknowledgment
  • NOTICE: Not available! (Replacement: RSS 36 I)
  • Thermoplastic enclosure
  • Electronic contact-free, coded system
  • Tampering protection by paired coding of sensor and actuator
  • Misaligned actuation possible
  • High repeat accuracy of the switching points
  • Max. length of the sensor chain 200 m
  • 2 short-circuit proof PNP safety outputs
  • Integral cross-short, wire-breakage and external voltage monitoring of the safety cables up to the control cabinet

Ordering data

Note (Delivery capacity)

不支持!

Product type description

CSP 11-34F2-D-M-ST

Article number (order number)

101208005

EAN (European Article Number)

4030661382029

eCl@ss number, version 12.0

27-27-26-06

eCl@ss number, version 11.0

27-27-24-04

eCl@ss number, version 9.0

27-27-24-04

ETIM number, version 7.0

EC001487

ETIM number, version 6.0

EC001487

Approvals - Standards

Certificates

cULus

General data

Standards

EN ISO 13849-1

EN IEC 60947-5-3

EN IEC 61508

Working principle

感应

Housing construction form

块体

Installation conditions (mechanical)

非冲洗

Sensor topology

串联传感器

Housing material

玻璃纤维,加强型热塑塑料

Active area

玻璃纤维,加强型热塑塑料

Reaction time, maximum

30 ms

Duration of risk, maximum

60 ms

Gross weight

140 g

General data - Features

Diagnostic output

Short circuit detection

Cross-circuit detection

Safety functions

Cascadable

Input for reset pushbutton, with edge monitoring

Input for enabling pushbutton, suitable for automatic start

On-site acknowledgment

Integral system diagnostics, status

Number of LEDs

3

Number of semi-conductor outputs with signaling function

1

Number of fail-safe digital outputs

2

Number of series-wiring of sensors

31

Safety classification

Vorschriften

EN IEC 60947-5-3

EN IEC 61508

Performance Level, up to

e

Category

4

PFH value

3.60 x 10⁻⁹ /h

Safety Integrity Level (SIL), suitable for applications in

3

Mission time

20 Year(s)

Mechanical data

Actuating panels

横向

Active area

横向

Mechanical data - Switching distances

Switch distance, typical

11 mm

Assured switching distance "ON" Sao

8 mm

Assured switching distance "OFF" Sar

15 mm

Note (switching distance)

All switching distances in accordance EN IEC 60947-5-3

Hysteresis (Switching distance), maximum

1.5 mm

Repeat accuracy R

0.5 mm

Note (Repeat accuracy R)

注意:轴向偏移长侧允许传感器和操动件的最大高度偏差(X)为30 mm (例如安装容差,或因防护门下垂)。轴向偏差 (y)最大± 8 mm。

Mechanical data - Connection technique

Note (length of the sensor chain)

根据输出电流,电缆长度和电缆截面会改变电压降

Termination

连接插头M12,8针

Mechanical data - Dimensions

Length of sensor

27 mm

Width of sensor

35 mm

Height of sensor

108.2 mm

Ambient conditions

Degree of protection

IP65

IP67

Ambient temperature

-25 ... +70 °C

Storage and transport temperature

-25 ... +85 °C

Resistance to vibrations

10 ... 55 Hz,振幅 1 mm

Restistance to shock

30 g / 11 ms

Protection class

II

Ambient conditions - Insulation values

Rated insulation voltage Ui

32 VAC/DC

Rated impulse withstand voltage Uimp

0.8 kV

Overvoltage category

III

Degree of pollution

3

Electrical data

Operating voltage

24 VDC -15 % / +10 %

No-load supply current I0, typical

100 mA

Rated operating voltage

24 VDC

Operating current

600 mA

Required rated short-circuit current

100 A

Utilisation category DC-12

24 VDC

Utilisation category DC-12

0.05 A

Utilisation category DC-13

24 VDC

Utilisation category DC-13

0.05 A

Note (Electrical data, Fuse rating)

(断路器)

Switching frequency, approx.

3 Hz

Utilisation category DC-12

24 VDC / 0.05 A

Electrical fuse rating, maximum

2 A

Electrical data - Safety digital outputs

Rated operating current (safety outputs)

250 mA

Output current, (fail-safe output), maximum

0.25 A

Design of control elements

P型

Voltage drop Ud, maximum

0.5 V

Leakage current Ir, maximum

0.5 mA

Voltage, Utilisation category DC-12

24 VDC

Current, Utilisation category DC-12

0.25 A

Voltage, Utilisation category DC-13

24 VDC

Current, Utilisation category DC-13

0.25 A

Electrical data - Digital Output

Design of control elements

P型

Electrical data - Diagnostic outputs

Operating current

50 mA

Voltage drop Ud, maximum

5 V

Voltage, Utilisation category DC-12

24 VDC

Current, Utilisation category DC-12

0.05 A

Electrical data - Electromagnetic compatibility (EMC)

Interfering radiation

IEC 61000-6-4

EMC rating

IEC 61000-6-2

Pin assignment

PIN 1

1A1 Ue: (1)

PIN 2

X1 安全输入 1

PIN 3

A2 GND

PIN 4

Y1 安全输出 1

PIN 5

OUT 诊断输出OUT

PIN 6

X2 安全输入 2

PIN 7

Y2 安全输出 2

PIN 8

IN 现场确认

Scope of delivery

Scope of delivery

操动件#必须单独订购.

Accessory

Recommendation (actuator)

CSP 34-S-1

Recommended safety switchgear

PROTECT PSC1

SRB-E-301ST

SRB-E-201LC

Note

Note (General)

当需要安全传感器CSP 34F2监控安全门时,应设置一个确认按钮,以便查看危险区域。当按钮被按下时,在CSP 34F2的复位输入端会产生一个24 VDC信号。

如果门关闭,安全输出将随着负信号边缘释放。门打开后,需要确认才能再次释放。

现场确认

语言条件

接线图示(电线)

下载最新版本的Adobe Reader


Schmersal India Pvt. Ltd., Plot No - G-7/1, Ranjangaon MIDC, Tal. - Shirur, Dist.- Pune 412 220

所涉及的详细信息和数据已经过仔细检查。 图像可能与原始图像有所不同。 您可在说明书中进一步获得技术数据。 可能会有技术修改和错误。

生成日期 2025/8/8 上午11:11