schmersal_s_icon.png

SRB-E-301ST

Artikelnummer: 103007672

  • Plug-in screw terminals with coding
  • STOP 0 Function
  • 1 oder 2-channel control
  • Start button / Auto-start
  • 1 Auxiliary contact
  • 3 safety contacts

Ordering data

PM_TYPE_NAME

SRB-E-301ST

PM_ORDER_NUMBER

103007672

SAP_EAN

4030661478470

CODE_ECLASS_V12P0

27-37-18-19

CODE_ECLASS_V11P0

27-37-18-19

CODE_ECLASS_V09P0

27-37-18-19

CODE_ETIM_V07P0

EC001449

CODE_ETIM_V06P0

EC001449

Approvals - Standards

PNV_NORM_CERTIFICATION

cULus

CCC

General data

NORM_STANDARD

EN IEC 62061

EN ISO 13849-1

EN IEC 60947-5-1

EN IEC 60947-5-3

EN IEC 60947-5-5

EN IEC 61508

EN IEC 60204-1

EN IEC 60947-1

NORM_CLIMATIC_STRESS

EN 60068-2-78

MAT_HOUSING

Kunststoff, glasfaserverstärkter Thermoplast, belüftet

SAP_WEIGHT_GROSS

175

General data - Features

YN_ELEC_FUSE

Ja

YN_WIRE_BREAKAGE_DETECT

Ja

YN_CROSS_SHORT_DETECT

Ja

YN_DETACHABLE_TERMINAL

Ja

YN_START_INPUT

Ja

YN_FEEDBACK_CIRCUIT

Ja

YN_AUTO_RESET_FUNC

Ja

YN_RESET_EDGE_DETECT

Ja

YN_EARTH_FAULT_DETECT

Ja

YN_INTEGR_DISPLAY_STATUS

Ja

YN_INTEGR_DISPLAY_ERR_CODE

Ja

NUM_OF_CONT_SUB

1

NUM_OF_LED

5

NUM_OF_NC

2

NUM_OF_NO

1

NUM_OF_SAFE_CONT_S0

3

Safety classification

SAFE_NORM_STANDARD

EN ISO 13849-1

EN IEC 62061

EN IEC 61508

SAFE_STOP_CAT

0

Safety classification - Relay outputs

SAFE_PERFORM_LEVEL_SROUT

e

SAFE_CAT_SROUT

4

SAFE_DIAG_COVER_LEVEL_SROUT

> 94

SAFE_PFH_VALUE_SROUT

1,25 x 10⁻⁸

SAFE_PFD_VALUE_SROUT

5,30 x 10⁻⁵

SAFE_SIL_SROUT

3

SAFE_MISSION_TIME_SROUT

20

SAFE_COMMON_CAUSE_FAIL_SROUT_MIN

65

Mechanical data

DESIGN_MECH_LIFETIME_SWITCH_MIN

10.000.000

DESIGN_MOUNTING

Schnellbefestigung für Normschiene nach DIN EN 60715

Mechanical data - Connection technique

APP_TERMINAL_DESIGNAT

IEC/EN 60947-1

REVIEW_ELEC_WIRING_GENERAL

starr oder flexibel

Schraubanschluss, steckbar

ELEC_CABLE_SECTION_MIN

0,25 mm²

ELEC_CABLE_SECTION_MAX

2,5 mm²

TRQ_TIGHTEN_TERMINAL_SCREW

0,5

Mechanical data - Dimensions

DIM_WIDTH_GENERAL

22,5

DIM_HEIGHT_GENERAL

98

DIM_DEPTH_GENERAL

115

Ambient conditions

DESIGN_IP_CLASS_HOUSING

IP40

DESIGN_IP_CLASS_CLEARANCE

IP54

DESIGN_IP_CLASS_TERMINAL

IP20

TEMP_AMB_GPV

-25 ... +60 °C

TEMP_STORAGE_AND_TRANSPORT_GPV

-40 ... +85 °C

REVIEW_RESIST_VIBRAT_EN60068_2_6

10 ... 55 Hz, Amplitude 0,35 mm

REVIEW_RESTIST_TO_SHOCK

30 g / 11 ms

Ambient conditions - Insulation values

VOLT_RATED_IMPULSE_WITHSTAND

4

DESIGN_OVERVOLT_CAT_IEC60664_1_ROMAN

III

DESIGN_DEG_OF_POLLUT_IEC60664_1

2

Electrical data

TIME_FREQ_RANGE

50

60

VOLT_OPERAT_GPV

24 VAC -15 % / +10 %
24 VDC -20 % / +20 %

ELEC_RIPPLE_VOLT_MAX

10

VOLT_RATED_OPERAT_AC

24

VOLT_RATED_OPERAT_DC

24

VOLT_RATED_CTRL_SUPPLY_AC50HZ_MIN

20,4

VOLT_RATED_CTRL_SUPPLY_AC50HZ_MAX

26,4

VOLT_RATED_CTRL_SUPPLY_AC60HZ_MIN

20,4

VOLT_RATED_CTRL_SUPPLY_AC60HZ_MAX

26,4

VOLT_RATED_CTRL_SUPPLY_DC_MIN

20,4

VOLT_RATED_CTRL_SUPPLY_DC_MAX

28,8

PWR_CONSUMPT_W

2,4

PWR_CONSUMPT_VA

7

ELEC_CONT_RESIST_MAX

0,1

NOTE_CONT_RESIST

in Neuzustand

TIME_DROP_OUT_DELAY_PWR_FAIL_TYP

10

TIME_DROP_OUT_DELAY_ESTOP_TYP

10

TIME_ON_DELAY_AUTO_START_TYP

150

TIME_ON_DELAY_RESET_TYP

150

TIME_SWITCH_FREQ_MAX

0,3

MAT_CONT_ELEC

Ag-Ni, selbstreinigend, zwangsgeführt

Electrical data - Safe relay outputs

VOLT_UTILISAT_CAT_AC15_SROUT

230

CURR_UTILISAT_CAT_AC15_SROUT

4

VOLT_UTILISAT_CAT_DC13_SROUT

24

CURR_UTILISAT_CAT_DC13_SROUT

4

VOLT_SWITCH_CPTY_SROUT_MIN

10

CURR_SWITCH_CPTY_SROUT_MIN

10

VOLT_SWITCH_CPTY_SROUT_MAX

250

CURR_SWITCH_CPTY_SROUT_MAX

6

Electrical data - Digital inputs

ELEC_CONDUCT_RESIST_MAX

40

Electrical data - Relay outputs (auxiliary contacts)

VOLT_SWITCH_CPTY_RELAY_SUB_MAX

24

CURR_SWITCH_CPTY_RELAY_SUB_MAX

1

Electrical data - Electromagnetic compatibility (EMC)

NORM_EMC_INTERFERENCE_RESIST

EMV-Richtlinie

Status indication

STATUS_LED_OPERAT_STATE

Interne Betriebsspannung Ui

Baustein-Status

Fehler-Codes

Other data

NOTE_TYPE_OF_APP

Sicherheits-Sensor

Schutzeinrichtung

drehbare Schutzeinrichtung

NOT-HALT-Taster

Seilzug-Notschalter

Sicherheits-Lichtvorhang

Sicherheits-Lichtschranken

Sicherheits-Schaltmatte

Sprachfilter

Download der aktuellen Version von Adobe Reader

Video ID: Mr-Safety-SRB-E

(Vimeo)


UK-Konformitätserklärung
UK Declaration of Conformity LOG_COM_lo1de01s
Company:K.A. Schmersal GmbH & Co. KG
Möddinghofe 30
42279 Wuppertal
Germany
Internet: www.schmersal.com
Declaration:We hereby, under sole responsibility, certify that the hereafter described components both in their basic design and construction conform to the relevant statutory requirements, regulations and designated standards of the United Kingdom.
Name of the component:SRB-E-201LC
SRB-E-201ST
SRB-E-301ST
Type:See ordering code
Description of the component:Relay safety combination for emergency-stop circuits, safety guard monitoring, magnetic safety switches, safety mats, two-hand controls and AOPDs
Relevant legislation:Supply of Machinery (Safety) Regulations2008
 Electromagnetic Compatibility Regulations2016
 The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations2012
Designated standards:EN ISO 13851:2019
EN ISO 13849-1:2015
EN ISO 13849-2:2012
EN 62061:2005 + AC:2010 + A1:2013 + A2:2015
IEC 61508 parts 1-7:2010
Notified body, which approved the full quality assurance system, referred to in Appendix X, 2006/42/EC:TÜV Rheinland Industrie Service GmbH
Am Grauen Stein
51105 Köln
ID n°: 0035
UK-Importer /
Person authorised for the compilation of the technical documentation:



Schmersal UK Ltd.
Paul Kenney
Unit 1, Sparrowhawk Close
Enigma Business Park
Malvern, Worcestershire, WR14 1GL
Place and date of issue:Wuppertal, March 14, 2023
 GRA_SIG_ksig-y24
 Authorised signature
Philip Schmersal
Managing Director

施迈赛工业开关制造(上海)有限公司, 上海市青浦区漕盈路3336号,

Die genannten Daten und Angaben wurden sorgfältig geprüft. Abbildungen können vom Original abweichen. Weitere technische Daten finden Sie in der Betriebsanleitung. Technische Änderungen und Irrtümer vorbehalten.

Generiert am: 23.06.2025, 09:26