schmersal_s_icon.png

AZM 200SK-T-SD2PA

Ürün numarası: 101193284

Downloads

TraceParts CAD Verileri
CADENAS CAD Verileri
Ürün tip tanımı:

AZM 200D(1)-T-1P2P2P(2)


(1)
SKVida bağlantısı
CCYay makara bağlantısı
ST1konektör M23, (8 + 1-kutup)
ST2konektör M12, 8-kutup
ST3Konektör fişi M23, 12-kutup

(2)
yokKilidi açma kuvveti
AKilitleme kuvveti
Bu tip anahtarı doğrultusundaki mümkün olan tüm cihazlar gönderilemez ve/veya teknik bakımdan uygulanamaz.
  • Guard locking monitored
  • serial diagnostic output
  • Thermoplastic enclosure
  • Electronic contact-free, coded system
  • Max. length of the sensor chain 200 m
  • 3 LEDs to show operating conditions
  • Sensor technology permits an offset between actuator and interlock of ± 5 mm  vertically and ± 1,5 mm horizontally
  • Intelligent diagnosis
  • Manual release

Ordering data

Note (Delivery capacity)

Phased-out product

Product type description

AZM 200SK-T-SD2PA

Article number (order number)

101193284

EAN (European Article Number)

4030661355313

eCl@ss number, version 12.0

27-27-26-03

eCl@ss number, version 11.0

27-27-26-03

eCl@ss number, version 9.0

27-27-26-03

ETIM number, version 7.0

EC002593

ETIM number, version 6.0

EC002593

Approvals - Standards

Certificates

cULus

General data

Standards

EN ISO 13849-1

EN IEC 60947-5-1

EN IEC 60947-5-3

EN IEC 61508

Working principle

endüktif

Housing material

Plastik, fiber cam takviyeli termoplastik

Reaction time, maximum

60 ms

Duration of risk, maximum

120 ms

Gross weight

598 g

General data - Features

Power to lock

Evet

Power to unlock

Evet

Actuator monitored

Evet

Solenoid interlock monitored

Evet

Serial diagnostics

Evet

Manual release

Evet

Short circuit detection

Evet

Safety functions

Evet

Integral system diagnostics, status

Evet

Number of safety contacts

2

Safety classification

Vorschriften

EN IEC 60947-5-3

EN IEC 61508

Safety classification - Interlocking function

Performance Level, up to

e

Category

4

PFH value

4,00 x 10⁻⁹ /h

Safety Integrity Level (SIL), suitable for applications in

3

Mission time

20 Year(s)

Safety classification - Interlocking function 2

Performance Level, up to

d

Category

3

PFH value

1,00 x 10⁻⁷ /h

Safety Integrity Level (SIL), suitable for applications in

2

Mission time

20 Year(s)

Mechanical data

Mechanical life, minimum

1.000.000 Operations

Holding force FZh in accordance with EN ISO 14119

2.000 N

Note (clamping force FZh)

1,000 N when used with the AZ/AZM201-B30 actuator, for indoor use.

Holding force Fmax, maximum

2.600 N

Note (clamping force Fmax)

1.300 N in Verbindung mit einem Betätiger AZ/AZM201-B30 für Innenanbau.

Latching force

30 N

Actuating speed, maximum

0,2 m/s

Tightening torque of the fastening screws for the housing cover, minimum

0,7 Nm

Tightening torque of the fastening screws for the housing cover, maximum

1 Nm

Note

Torx T10

Mechanical data - Connection technique

Note (length of the sensor chain)

Cable length and cross-section change the voltage drop dependiing on the output current

Note (series-wiring)

Unlimited number of devices, oberserve external line fusing, max. 31 devices in case of serial diagnostic SD

Termination

Vida bağlantısı M20 x 1.5

Cable section, minimum

0,25 mm²

Cable section, maximum

1,5 mm²

Note

Kablo kısmı hakkındaki bütün göstergeler iletken yüksüklerini dahil ediyor.

Wire cross-section, minimum

23 AWG

Wire cross-section, maximum

15 AWG

Mechanical data - Dimensions

Length of sensor

50 mm

Width of sensor

40 mm

Height of sensor

220 mm

Ambient conditions

Degree of protection

IP67

Ambient temperature

-25 ... +50 °C

Storage and transport temperature

-25 ... +85 °C

Resistance to vibrations

10 … 55 Hz, Genlik 1 mm

Restistance to shock

30 g / 11 ms

Protection class

II

Ambient conditions - Insulation values

Rated insulation voltage Ui

32 VDC

Rated impulse withstand voltage Uimp

0,8 kV

Overvoltage category

III

Degree of pollution

3

Electrical data

Operating voltage

24 VDC -15 % / +10 %

Rated operating voltage

24 VDC

Operating current

1.200 mA

Length of cable, maximum

200 m

Time to readiness, maximum

4.000 ms

Switching frequency, approx.

1 Hz

Electrical data - Magnet control

Switching thresholds

-3 V … 5 V (Low)

15 V … 30 V (High)

Magnet switch-on time

100 %

Electrical data - Safety digital inputs

Switching thresholds

−3 V … 5 V (Low)

15 V … 30 V (High)

Electrical data - Safety digital outputs

Voltage drop Ud, maximum

4 V

Leakage current Ir, maximum

0,5 mA

Voltage, Utilisation category DC-13

24 VDC

Current, Utilisation category DC-13

0,25 A

Note, Utilisation category DC-13

Gilt für die Ausgänge Y1 und Y2

Electrical data - Diagnostic outputs

Operating current

100 mA

Voltage drop Ud, maximum

4 V

Voltage, Utilisation category DC-13

24 VDC

Current, Utilisation category DC-13

0,05 A

Electrical data - Serial diagnostic SD

Designation, Serial diagnostic SD

OUT

Operation current

150 mA

Design of control elements

short-circuit proof, p-type

Wiring capacitance

50 nF

Status indication

Note (LED switching conditions display)

Anahtarlama koşulu: sarı LED

Hata işlevli kusur: kırmızı LED

Besleme gerilimi UB: yeşil LED

Scope of delivery

Scope of delivery

Actuator must be ordered separately.

Üçken anahtar hedef AZM 200

Accessory

Recommendation (actuator)

AZ/AZM 200-B1

Note

Note (General)

As long as the actuating unit remains inserted in the solenoid interlock, the unlocked safety guard can be relocked. In this case, the safety outputs are re-enabled, so that the safety guard must not be opened.

Note (Actuator monitored)

Emniyetli çıkışlar Y1, Y2

Note (Solenoid interlock monitored)

Emniyetli çıkışlar Y3, Y4

Dil filtresi

Kablo döşeme örneği (elektr. kablolama)

Adobe Reader’ın son sürümünü indirin


Schmersal India Pvt. Ltd., Plot No - G-7/1, Ranjangaon MIDC, Tal. - Shirur, Dist.- Pune 412 220

Veriler ve ayrıntılar dikkatli bir şekilde kontrol edilmişlerdir. Görüntüler orijinalden farklı olabilir. Daha fazla teknik veri kılavuzda bulunabilir. Teknik değişiklikler ve hatalar olabilir.

Udarbejdet d. 25.04.2025 18:18