SRB200EXi-1R
SRB200EXi-1R
Downloads
- Reset with trailing edge
- 2 safety contacts
- Suitable for signal processing of emergency stop control devices, interlocking equipment, etc
Ordering data
Product type description |
SRB200EXi-1R |
Article number (order number) |
103037575 |
EAN (European Article Number) |
4030661542737 |
eCl@ss number, version 12.0 |
27-37-18-19 |
eCl@ss number, version 11.0 |
27-37-18-19 |
eCl@ss number, version 9.0 |
27-37-18-19 |
ETIM number, version 7.0 |
EC001449 |
ETIM number, version 6.0 |
EC001449 |
Approvals - Standards
Certificates |
ATEX IECEx INMETRO PESO |
Explosion protection
Explosion protection: regulations |
EN IEC 60079-0 EN 60079-11 EN IEC 60079-15 |
Explosion protection zones |
2 |
Explosion protection category |
3G |
Explosion protection designation |
D II 3 G Ex nA nC IIC T5 Gc (Installation SRB, in Zone 2) D II (2) G [Ex ib Gb] IIC D II (2) D [Ex ib Db] IIIC |
General data
Climatic stress |
EN 60068-2-78 |
Housing material |
Plastik, fiber cam takviyeli termoplastik, havalandırılmış |
Gross weight |
264 g |
General data - Features
Wire breakage detection |
Evet |
Cross-circuit detection |
Evet |
Earth connection detection |
Evet |
Integral system diagnostics, status |
Evet |
Number of LEDs |
5 |
Number of normally closed (NC) |
2 |
Number of safety contacts |
2 |
Safety classification |
Vorschriften |
EN ISO 13849-1 EN IEC 60947-5-1 EN IEC 61508 |
Stop-Category |
0 |
Safety classification - Relay outputs |
Performance Level, stop 0, up to |
e |
Category, Stop 0 |
4 |
Diagnostic Coverage (DC) Level, Stop 0 |
≥ 99 % |
PFH value, Stop 0 |
2,00 x 10⁻⁸ /h |
Safety Integrity Level (SIL), Stop 0, suitable for applications in |
3 |
Mission time |
15 Year(s) |
Common Cause Failure (CCF), minimum |
65 |
Mechanical data
Mechanical life, minimum |
10.000.000 Operations |
Mounting |
EN 60715 e uygun standart DIN rayının üzerine kilitlenir |
Mechanical data - Connection technique
Terminal designations |
IEC/EN 60947-1 |
Cable section, minimum |
0,25 mm² |
Cable section, maximum |
2,5 mm² |
Tightening torque of Clips |
0,6 Nm |
Mechanical data - Dimensions
Width |
22,5 mm |
Height |
100 mm |
Depth |
121 mm |
Ambient conditions
Degree of protection of the enclosure |
IP40 |
Degree of protection of the mounting space |
IP54 |
Degree of protection of clips or terminals |
IP20 |
Ambient temperature |
-25 ... +60 °C |
Storage and transport temperature |
-40 ... +85 °C |
Resistance to vibrations |
10 ... 55 Hz, Genlik 0.35 mm |
Restistance to shock |
30 g / 11 ms |
Ambient conditions - Insulation values
Rated impulse withstand voltage Uimp |
4 kV |
Overvoltage category |
III |
Degree of pollution |
2 |
Electrical data
Operating voltage |
24 VDC -10 % / +20 % |
Ripple voltage |
10 % |
Current consumption |
57 mA |
Rated operating voltage |
24 VDC |
Rated AC voltage for controls at DC minimum |
20,4 VDC |
Rated control voltage at DC, maximum |
28,8 VDC |
Utilisation category AC-15 |
230 VAC |
Utilisation category AC-15 |
2 A |
Utilisation category DC-13 |
24 VDC |
Utilisation category DC-13 |
2 A |
Electrical power consumption |
3 W |
Contact resistance, maximum |
0,1 Ω |
Note (Contact resistance) |
yeni durumda |
Drop-out delay in case of power failure, typically |
20 ms |
Drop-out delay in case of "emergency stop", maximum |
20 ms |
Pull-in delay at automatic start, maximum, typically |
300 ms |
Pull-in delay at RESET, typically |
20 ms |
Material of the contacts, electrical |
Ag-Ni 10 ve 0.2 µm altın kaplama |
Electrical data - Digital inputs
Conduction resistance, maximum |
30 Ω |
Electrical data - Electromagnetic compatibility (EMC)
EMC rating |
EMC-Directive |
Other data
Note (applications) |
Güvenlik sensörü Koruma sistemi Acil Stop butonu Halatlı acil stop anahtarları |
Note
Note (General) |
Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit. |
Wiring example
Note (Wiring diagram) |
The wiring diagram is shown with guard doors closed and in de-energised condition. Monitoring 1 guard door(s), each with a magnetic safety sensor of the BNS range If only one external relay or contactor is used to switch the load, the system can be classified in Control Category 3 to ISO 13849-1, if exclusion of the fault “Failure of the external contactor” can be substantiated and is documented, e.g. by using a reliable down-rated contactor. A second contactor leads to an increase in the level of security by redundant switching to switch the load off. To secure a guard door up to PL e and Category 4 The feedback circuit monitors the position of the contactors KA and KB. Automatic start: The automatic start is programmed by connecting the feedback circuit to the terminals X1/X2. If the feedback circuit is not required, establish a bridge. |
Dil filtresi
Veri sayfası
Çalışma Talimatları ile Uygunluk beyanı
IECEx sertifikasyonu
INMETRO sertifikasyonu
PESO-Zertifikat
Broşür
Adobe Reader’ın son sürümünü indirin
Ürün resmi (katalog özel fotoğraf)
Boyutsal resim temel bileşeni
Sembol (teknik standart)
Kablo döşeme örneği
EU Declaration of Conformity | ![]() |
Original | K.A. Schmersal GmbH & Co. KG Möddinghofe 30 42279 Wuppertal Germany Internet: www.schmersal.com |
Declaration: | We hereby certify that the hereafter described components both in their basic design and construction conform to the applicable European Directives. |
Name of the component: | SRB200EXi-1R |
Type: | See ordering code |
Marking: | D II 3 (2) G Ex ec nC [ib Gb] IIC T5 Gc D II (2) D [Ex ib Db] IIIC |
Description of the component: | Safety-monitoring module for emergency stop circuits and guard door monitoring |
Relevant Directives: | Machinery Directive | 2006/42/EC |
EMC-Directive | 2014/30/EU | |
Explosion Protection Directive (ATEX) | 2014/34/EU | |
RoHS-Directive | 2011/65/EU |
Applied standards: | EN IEC 60079-0:2018 EN 60079-7:2015 EN IEC 60079-7:2015 / A1:2018 EN 60079-11:2012 EN IEC 60079-15:2019 EN 60947-5-1:2017 + AC:2020 EN ISO 13849-1:2015 EN ISO 13849-2:2012 |
Notified body for certification of the QA system in accordance with Appendix X in accordance with 2006/42/EC, Appendix IV in accordance with 2014/34/EU and for ATEX certification: | TÜV Rheinland Industrie Service GmbH Am Grauen Stein, 51105 Köln ID n°: 0035 |
Type Examination Certificate: | TÜV 22 ATEX 8837 X |
This certificate refers only to the certification of the products in accordance with the Explosion Protection Directive 2014/34/EU (ATEX). Product conformity in accordance with the Machinery Directive 2006/42/EC is declared by the manufacturer under its own responsibility. |
Person authorised for the compilation of the technical documentation: | Oliver Wacker Möddinghofe 30 42279 Wuppertal |
Place and date of issue: | Wuppertal, October 30, 2024 |
![]() |
Authorised signature Philip Schmersal Managing Director |
Schmersal India Pvt. Ltd., Plot No - G-7/1, Ranjangaon MIDC, Tal. - Shirur, Dist.- Pune 412 220
Veriler ve ayrıntılar dikkatli bir şekilde kontrol edilmişlerdir. Görüntüler orijinalden farklı olabilir. Daha fazla teknik veri kılavuzda bulunabilir. Teknik değişiklikler ve hatalar olabilir.
Udarbejdet d. 23.02.2025 05:40