Approvals - Standards

Certificates

CCC

General data

Standards

DIN VDE 0660-208

EN IEC 60947-5-2

Housing construction form

Cylinder, thread

Installation conditions (mechanical)

not flush

Housing material

Plastic

Active area

Plastic

Material of the nuts

Plastic

Material of the washer

Perbunan

Gross weight

134 g

General data - Features

Integral system diagnostics, status

Yes

Cable sleeve

No

Number of cable wires

3

Mechanical data

Tightening torque of nuts, maximum

3 Nm

Mechanical data - Switching distances

Switching distance Sn

10 mm

Nominal switching distance Sn

10 mm

Note (switching distance)

All switching distances in accordance EN IEC 60947-5-2

Mechanical data - Connection technique

Length of cable

3 m

Termination

Cable H03VV-F

Number of cable wires

3

Wire cross-section

0.5 mm2

Material of the Cable mantle

PVC

Mechanical data - Dimensions

Diameter of sensor

18 mm

ISO thread of the sensor

M18x1

width across flats

24 BK

Length of sensor

79 mm

Diameter of the Mounting clamp

M18x1

Ambient conditions

Degree of protection

IP67

Resistance to vibrations

10 … 55 Hz, amplitude 1 mm

Restistance to shock

30 g / 11 ms

Protection class

II

Ambient conditions - Insulation values

Rated impulse withstand voltage Uimp

4 kV

Electrical data

Rated supply frequency, minimum

45 Hz

Rated supply frequency, maximum

65 Hz

Type of voltage range

AC

Operating current, minimum

10 mA

Operating current

500 mA

Switching element

Normally open contact (NO)

Protection circuit integrated

inductive interference protection

Switching frequency, approx.

10 Hz

Electrical data - Digital Output

Voltage drop Ud, maximum

4.5 V

Current at Voltage drop Ud

0.5 A

Design of control elements

Two-wire

Current leakage Ir, maximum

1 mA

Status indication

Note (Integral System Diagnostics, status )

yellow LED