SLC 210-E/R1060-20- 12
SLC 210-E/R1060-20- 12
Downloads
- NOTICE: Not available! (Replacement: SLC 220)
- Control Category 2
Ordering data
Note (Delivery capacity) |
Not available! |
Product type description |
SLC 210-E/R1060-20- 12 |
Article number (order number) |
101160929 |
eCl@ss number, version 12.0 |
27-27-27-04 |
eCl@ss number, version 11.0 |
27-27-27-04 |
eCl@ss number, version 9.0 |
27-27-27-04 |
ETIM number, version 7.0 |
EC002549 |
ETIM number, version 6.0 |
EC002549 |
General data
Standards |
EN IEC 61496-2 EN IEC 61496-1 |
Housing material |
Aluminium |
Reaction time, maximum |
18 ms |
Gross weight |
5,800 g |
General data - Features
Beam coding available |
Yes |
Integral system diagnostics, status |
Yes |
Integral system diagnostics |
Yes |
Number of fail-safe digital outputs |
2 |
Number of beams |
105 |
Safety classification |
Safety type in accordance with IEC 61496-1 |
2 |
Mechanical data
Height of the protection field |
1,060 mm |
Range, protection field, minimum |
0 m |
Range, protection field, maximum |
6 m |
Wave length of the laserdiode |
950 nm |
Mechanical data - Connection technique
Termination |
Connector |
Terminal connector, Recipient |
Connector plug M12, 5-pole |
Terminal, Connector, Transmitter |
Connector plug M12, 5-pole |
Length of the connectable cable, maximum |
100 m |
Mechanical data - Dimensions
Length of sensor |
35 mm |
Width of sensor |
45 mm |
Height of sensor |
1,161 mm |
Ambient conditions
Degree of protection |
IP65 |
Ambient temperature |
+0 ... +55 °C |
Storage and transport temperature |
-20 ... +70 °C |
Protection class |
III |
Electrical data
Switching voltage OSSD, HIGH signal |
24 V |
Electrical power consumption of the receiver |
3 W |
Electrical power consumption of the transmitter |
2 W |
Electrical data - Safety digital outputs
Output current, (fail-safe output), maximum |
0.5 A |
Design of control elements |
p-type |
Scope of delivery
Scope of delivery |
Emitter + receiver, mounting angle, T-slot nuts |
Accessory
Recommended safety switchgear |
SCR 402R-301 |
Note
Note (General) |
Im In case of failure (interruption of the 0 V supply) the maximum leakage current is 0.3 mA. |
Language filter
Datasheet
Mounting and wiring instructions
Download the latest version of Adobe Reader
Product picture (catalogue individual photo)
Dimensional drawing basic component
Schmersal India Pvt. Ltd., Plot No - G-7/1, Ranjangaon MIDC, Tal. - Shirur, Dist.- Pune 412 220
The details and data referred to have been carefully checked. Images may diverge from original. Further technical data can be found in the manual. Technical amendments and errors possible.
Generated on: 18/11/2024, 12:06 pm