TR 235 ST-AS
Item number:101213945
Archive

Product features
- AS-Interface M12 connector
- Metal enclosure
- Wide range of alternative actuators
- Good resistance to oil and petroleum spirit
- 30 mm x 63,5 mm x 30 mm
- Actuator heads can be repositioned by 4 x 90°
- Mounting details to EN 50047
- AS-Interface LED and status display
- Integrated AS-Interface
- Suitable for AS-i Power24
Ext Cat Orde
Note (Delivery capacity)Not available!
Product type descriptionTR 235 ST-AS
Article number (order number)101213945
EAN (European Article Number)4030661404202
eCl@ss number, version 12.027-27-26-01
eCl@ss number, version 11.027-27-26-01
eCl@ss number, version 9.027-27-26-01
ETIM number, version 7.0EC000030
ETIM number, version 6.0EC000030
Ext Cat Norm
CertificatesASi-SaWcULus
Ext Cat Prod
StandardsEN IEC 60947-5-1EN IEC 61508EN IEC 62026-2EN ISO 13849-1
Housing construction formNorm construction design
Actuator type to EN 50047C
Housing materialMetal, zinc die-cast
Housing coating materialpainted
Gross weight195g
Ext Cat Prod Feature
Safety functionsYes
Integral system diagnostics, statusYes
Number of auxiliary contacts0
Number of safety contacts2
Ext Cat Safe
StandardsEN IEC 61508
Performance Level, up toc
Category1
PFH value1.14 x 10⁻⁶/h
Note (PFH-value)up to max. 100,000 switching cycles/year
Safety Integrity Level (SIL), suitable for applications in1
Mission time20Year(s)
Ext Cat Safe Fau Exc
Please note:Can be used when fault exclusion for dangerous damage to the 1-channel mechanism is permissible and sufficient protection against manipulation is guaranteed.
Performance Level, up tod
Category3
PFH value1.01 x 10⁻⁷/h
Note (PFH-value)up to max. 100,000 switching cycles/year
Safety Integrity Level (SIL), suitable for applications in2
Mission time20Year(s)
Ext Cat Mech
Actuating elementRoller plunger
Mechanical lifetime, minimum1,000,000Operations
Actuating force, minimum9N
Positive break force, minimum19N
Actuating speed, maximum1m/s
Ext Cat Mech Dat Ele
TerminationConnector plug M12, 5-pole, can be rotated
Material of the connector (electrical)Metal film
Ext Cat Mech Dat Dim
Length of sensor30mm
Width of sensor30mm
Height of sensor106mm
Ext Cat Ambi
IP Degree of protectionIP67
Ambient temperature-30 ... +60 °C
Storage and transport temperature-40 ... +85 °C
Relative humidity, minimum30%
Relative humidity, maximum95%
Note (Relative humidity)non-condensingnon-icing
Resistance to vibrations10 … 150 Hz, amplitude 0.35 mm / 5 g
Restistance to shock30 g / 11 ms
Ext Cat Ambi Iso Iec
Rated insulation voltage Ui32 VDC
Rated impulse withstand voltage Uimp0.8kV
Ext Cat Elec
Current consumption50mA
Switching elementOpener (NC)
Switching principleSlow action
Maximum switching frequency5,000/h
Ext Cat Elec Dat Asi
Rated operating voltage18 ... 31.6 VDC (Protection against polarity reversal)
Ext Cat Elec Asi Spe
AS-i Version V 3.0
AS-i Profile S-0.B.F.F
AS-i Input, Channel 1Data bits DI 0 / DI 1 = dynamic code transmission
AS-i Input, Channel 2Data bits DI 2 / DI 3 = dynamic code transmission
AS-i Outputs, DO 0 … DO 3No Function
AS-i Parameter bits, P0Channel 2 switched
AS-i Parameter bits, P1 ... P3No function
AS-i Input module address0
Note (AS-i Input module address)Preset to address 0, can be changed through AS-interface bus master or hand-held programming device
Ext Cat Disp
Note (LED switching conditions display)(1) LED yellow: Channel 1 / AS-i SaW Bit 0.1(2) LED green-red (AS-i Duo LED):Supply voltage / Communication error / Slave address = 0(3) LED yellow: Channel 2 / AS-i SaW Bit 2.3
Ext Cat Conn
PIN 1AS-Interface +
PIN 2n.c.
PIN 3AS-Interface -
PIN 4n.c.
PIN 5Functional earth connection
The details and data referred to have been carefully checked. Images may diverge from original. Further technical data can be found in the manual. Technical amendments and errors possible.
Generated on: 28/11/2026, 12:39 pm