IFL 4-12-10P 3,0M
IFL 4-12-10P 3,0M
Downloads
- Design M12
Ordering data
| Product type description |
IFL 4-12-10P 3,0M |
| Article number (order number) |
101104647 |
| EAN (European Article Number) |
4030661271774 |
| eCl@ss number, version 12.0 |
27-27-40-01 |
| eCl@ss number, version 11.0 |
27-27-01-01 |
| eCl@ss number, version 9.0 |
27-27-01-01 |
| ETIM number, version 7.0 |
EC002714 |
| ETIM number, version 6.0 |
EC002714 |
Approvals - Standards
| Certificates |
CCC |
General data
| Standards |
DIN VDE 0660-208 EN IEC 60947-5-2 |
| Housing construction form |
Cylinder, thread |
| Installation conditions (mechanical) |
not flush |
| Housing material |
Brass |
| Housing coating material |
nickel-plated |
| Active area |
Plastic |
| Material of the nuts |
Nickel plated brass |
| Gross weight |
87 g |
General data - Features
| Integral system diagnostics, status |
Yes |
| Number of cable wires |
3 |
Mechanical data
| Tightening torque of nuts, maximum |
15 Nm |
| Note (Tightening torque of nuts) |
In the shell core area: max. 500 Ncm |
Mechanical data - Switching distances
| Nominal switching distance Sn |
4 mm |
| Note (switching distance) |
All switching distances in accordance EN IEC 60947-5-2 |
Mechanical data - Connection technique
| Length of cable |
3 m |
| Termination |
Cable |
| Number of cable wires |
3 |
| Wire cross-section |
0.14 mm2 |
| Material of the Cable mantle |
PVC |
Mechanical data - Dimensions
| ISO thread of the sensor |
M12 |
| width across flats |
17 BK |
| Length of sensor |
50 mm |
Ambient conditions
| Degree of protection |
IP67 |
| Ambient temperature |
-25 ... +70 °C |
| Resistance to vibrations |
10 … 55 Hz, amplitude 1 mm |
| Restistance to shock |
30 g / 11 ms |
| Protection class |
II |
Electrical data
| Operating voltage |
10 ... 30 VDC |
| Type of voltage range |
DC |
| No-load supply current I0, typical |
3 mA |
| Rated operating voltage |
10 ... 30 VDC |
| Operating current |
200 mA |
| Switching element |
Normally open contact (NO) |
| Protection circuit integrated |
inductive interference protection Protection against polarity reversal Surge protection Max. fuse rating |
| Switching frequency, approx. |
500 Hz |
Electrical data - Digital Output
| Voltage drop Ud, maximum |
1.2 V |
| Current at Voltage drop Ud |
0.2 A |
| Design of control elements |
p-type |
Status indication
| Note (Integral System Diagnostics, status ) |
yellow LED |
Note
| Note (General) |
Instead of nuts, a mounting clamp can be provided. |
Language filter
Datasheet
Operating instructions (supplementary sheet/quick guide)
EC Declaration of conformity
CCC certification
Download the latest version of Adobe Reader
Product picture (catalogue individual photo)
Dimensional drawing basic component
K.A. Schmersal GmbH & Co. KG, Möddinghofe 30, 42279 Wuppertal
The details and data referred to have been carefully checked. Images may diverge from original. Further technical data can be found in the manual. Technical amendments and errors possible.
Generated on: 23/10/2025, 14:48