RSS260-I2-SD-ST
RSS260-I2-SD-ST
Product type description: RSS260-(1)-(2)-(3)-(4)-(5) |
(1) | |
without | Standard coding |
I1 | Individual coding |
I2 | Individual coding, multiple teaching |
(2) | |
D | With diagnostic output |
SD | With serial diagnostic function 1) |
(3) | |
without | Standard version without feedback circuit monitoring EDM (External Device Monitoring) |
F0 | EDM with automatic reset 1) |
F1 | EDM with manual reset 1) |
(4) | |
without | Without EMERGENCY STOP |
Q | Acknowledge input error with EMERGENCY STOP 1) |
(5) | |
without | Connecting cable (lenght in m) |
ST | Connector plug M8, 8-pole |
LSTM12-8-0,25M | Cable 0.25 m long with connector M12, 8-pole |
LSTM8-8-0,1M | Cable 0.1 m long with connector M8, 8-pole |
LSTM12-5-0.25M | Cable 0.25 m long with connector M12, 5-pole |
(*) | |
1) | only for versions -ST, -LSTM12-8-0.25M and -LSTM8-8-0.1M |
- Repeated individual coding with RFID technology
- Coding level "High" according to ISO 14119
- 1 x connector plug M8
- Frontal and lateral actuation enabled
- Max. 31 sensors can be wired in series.
- Thermoplastic enclosure
- Simple mounting without additional angle
- RFID-technology for needs-based protection against tampering
Ordering data
Product type description |
RSS260-I2-SD-ST |
Article number (order number) |
103003603 |
EAN (European Article Number) |
4030661436463 |
eCl@ss number, version 12.0 |
27-27-46-01 |
eCl@ss number, version 11.0 |
27-27-24-03 |
eCl@ss number, version 9.0 |
27-27-24-03 |
ETIM number, version 7.0 |
EC001829 |
ETIM number, version 6.0 |
EC001829 |
Approvals - Standards
|
TÜV cULus FCC IC ANATEL |
General data
Standards |
EN ISO 13849-1 EN IEC 60947-5-3 EN IEC 61508 |
Coding |
Individuelle Codierung, mehrfach anlernbar |
Coding level according to EN ISO 14119 |
hoch |
Working principle |
RFID |
Frequency band RFID |
125 kHz |
Transmitter output RFID, maximum |
-6 dB/m |
Housing construction form |
Quader |
Installation conditions (mechanical) |
nicht bündig |
Sensor topology |
Reihenschaltungsgerät |
Housing material |
Kunststoff, Thermoplast, selbstverlöschend |
Active area |
Kunststoff, Thermoplast |
Reaction time, maximum |
100 ms |
Duration of risk, maximum |
200 ms |
Reaction time, switching off safety outputs via actuator, maximum |
100 ms |
Gross weight |
60 g |
General data - Features
Serial diagnostics |
Ja |
Short circuit detection |
Ja |
Cross-circuit detection |
Ja |
Series-wiring |
Ja |
Safety functions |
Ja |
Cascadable |
Ja |
Integral system diagnostics, status |
Ja |
Number of LEDs |
3 |
Number of poles |
8 |
Number of fail-safe digital outputs |
2 |
Number of series-wiring of sensors |
31 |
Safety classification |
Standards |
EN ISO 13849-1 EN IEC 61508 |
Performance Level, up to |
e |
Category |
4 |
PFH value |
6,80 x 10⁻¹⁰ /h |
PFD value |
1,20 x 10⁻⁴ |
Safety Integrity Level (SIL), suitable for applications in |
3 |
Mission time |
20 Year(s) |
Mechanical data
Actuating panels |
seitlich vorderseitig |
Active area |
seitlich vorne |
Mounting |
Zur Montage der Sensoren reichen üblicherweise 20 mm Schraubenlänge. Bei Verwendung der Montageplatten werden 25 mm lange Schrauben empfohlen. |
Type of the fixing screws |
2x M4 |
Tightening torque of the fixing screws, maximum |
0,8 Nm |
Mechanical data - Switching distances according EN IEC 60947-5-3
Typical switching distance, frontal |
12 mm |
Typical switching distance, lateral |
9 mm |
Assured switching distance "ON", frontal |
10 mm |
Assured switching distance "OFF", frontal |
18 mm |
Assured switching distance "ON", lateral |
6 mm |
Assured switching distance "OFF", lateral |
15 mm |
Note (Sao) |
Die Angaben des gesicherten Schaltabstands Sao beziehen sich auf einen Temperaturbereich −10 °C … +60 °C. Bei einem Temperaturbereich von −28 °C … +65 °C reduziert sich Sao um 2 mm. |
Note (switching distance) |
Axialer Versatz Sicherheits-Sensor und Betätiger tolerieren einen horizontalen und vertikalen Versatz zueinander. Der mögliche Versatz ist abhängig vom Abstand der aktiven Flächen von Sensor und Betätiger. Innerhalb des Toleranzbereiches ist der Sensor aktiv geschaltet. |
Hysteresis (Switching distance), maximum |
2 mm |
Repeat accuracy R |
0,5 mm |
Note (Repeat accuracy R) |
Seitlicher Versatz: Die lange Seitenfläche erlaubt einen max. Höhenversatz (x) von Sensor und Betätiger um 8 mm (z.B. Montagetoleranz oder durch Absacken der Schutztür). Der Querversatz (y) beträgt max. ± 18 mm (siehe Abbildung: Funktionsweise).Mindestabstand von zwei Sensorsystemen 100 mm |
Mechanical data - Connection technique
Note (length of the sensor chain) |
Leitungslänge und Leitungsquerschnitt verändern den Spannungsfall in Abhängigkeit vom Ausgangsstrom |
Note (series-wiring) |
Anzahl der Geräte unbegrenzt, externen Leitungsschutz beachten, max. 31 Geräte bei serieller Diagnose SD |
Termination |
Steckverbinder M8, 8-polig |
Mechanical data - Dimensions
Length of sensor |
29,5 mm |
Width of sensor |
39,2 mm |
Height of sensor |
18 mm |
Ambient conditions
Degree of protection |
IP65 IP67 |
Ambient temperature |
-28 ... +65 °C |
Storage and transport temperature |
-28 ... +85 °C |
Relative humidity, maximum |
93 % |
Note (Relative humidity) |
nicht kondensierend nicht vereisend |
Resistance to vibrations |
10 … 55 Hz, Amplitude 1 mm |
Restistance to shock |
30 g / 11 ms |
Permissible installation altitude above sea level, maximum |
2.000 m |
Ambient conditions - Insulation values
Rated insulation voltage Ui |
32 VDC |
Rated impulse withstand voltage Uimp |
0,8 kV |
Overvoltage category |
III |
Degree of pollution |
3 |
Electrical data
Operating voltage |
24 VDC -15 % / +10 % (stabilisiertes PELV-Netzteil) |
Operating current, minimum |
0,5 mA |
No-load supply current I0, typical |
35 mA |
Rated operating voltage |
24 VDC |
Operating current |
600 mA |
Required rated short-circuit current |
100 A |
Time to readiness, maximum |
2.000 ms |
Switching frequency, maximum |
1 Hz |
Electrical fuse rating, maximum |
2 A |
Electrical data - Safety digital inputs
Designation, Safety inputs |
X1 und X2 |
Current consumption of the safety inputs |
5 mA |
Test pulse duration, maximum |
1 ms |
Test pulse interval, minimum |
100 ms |
Classification ZVEI CB24I, Sink |
C1 |
Classification ZVEI CB24I, Source |
C1 C2 C3 |
Electrical data - Safety digital outputs
Designation, Safety outputs |
Y1 und Y2 |
Rated operating current (safety outputs) |
250 mA |
Output current, (fail-safe output), maximum |
0,25 A |
Design of control elements |
kurzschlussfest, p-schaltend |
Voltage drop Ud, maximum |
1 V |
Leakage current Ir, maximum |
0,5 mA |
Voltage, Utilisation category DC-12 |
24 VDC |
Current, Utilisation category DC-12 |
0,25 A |
Voltage, Utilisation category DC-13 |
24 VDC |
Current, Utilisation category DC-13 |
0,25 A |
Test pulse interval, typical |
1000 ms |
Test pulse duration, maximum |
1 ms |
Classification ZVEI CB24I, Source |
C2 |
Classification ZVEI CB24I, Sink |
C1 C2 |
Electrical data - Serial diagnostic SD
Designation, Serial diagnostic SD |
OUT |
Operation current |
150 mA |
Design of control elements |
kurschlussfest |
Wiring capacitance |
50 nF |
Electrical data - Electromagnetic compatibility (EMC)
Interfering radiation |
IEC 61000-6-4 |
Status indication
Note (LED switching conditions display) |
(1) grüne LED: Versorgungsspannung gelbe LED: Betriebszustand rote LED: Fehler |
Pin assignment
PIN 1 |
A1 Ue: weiß |
PIN 2 |
X1 Sicherheitseingang 1: braun |
PIN 3 |
A2 GND: grün |
PIN 4 |
Y1 Sicherheitsausgang 1: gelb |
PIN 5 |
OUT serieller Diagnoseausgang: grau |
PIN 6 |
X2 Sicherheitseingang 2: rosa |
PIN 7 |
Y2 Sicherheitsausgang 2: blau |
PIN 8 |
IN serieller Diagnoseeingang: rosa |
Scope of delivery
Scope of delivery |
Der Betätiger ist nicht im Lieferumfang enthalten. |
Accessory
Recommendation (actuator) |
RST16-1 RST-U-2 RST260-1 |
Recommended safety switchgear |
PROTECT PSC1 SRB-E-301ST SRB-E-201LC |
Note
Note (General) |
Anforderungen an die Auswertung: Zweikanaliger Sicherheitseingang, geeignet für p-schaltende Sensoren mit Schließerfunktion. Die Funktionstests der Sensoren mit zyklischem Abschalten der Sensorausgänge für max. 1 ms müssen von der Auswertung toleriert werden. Eine Querschlusserkennung in der Auswertung ist nicht notwendig. |
Sprachfilter
Datenblatt
Betriebsanleitung und Konformitätserklärung
ANATEL-Zertifikat
UL-Zertifikat
FCC-Zertifikat
IC-Zertifikat
Broschüre
SISTEMA-VDMA Bibliothek/Library
Download der aktuellen Version von Adobe Reader
Produktbild (Katalogeinzelphoto )
Maßzeichnung Grundgerät
Video ID: SD-Interface-Mr-Safety
EU-Konformitätserklärung |
Original | K.A. Schmersal GmbH & Co. KG Möddinghofe 30 42279 Wuppertal Germany Internet: www.schmersal.com |
Erklärung: | Hiermit erklären wir, dass die nachfolgend aufgeführten Bauteile aufgrund der Konzipierung und Bauart den Anforderungen der unten angeführten Europäischen Richtlinien entsprechen. |
Bezeichnung des Bauteils: | RSS260 |
Typ: | siehe Typenschlüssel |
Beschreibung des Bauteils: | Berührungslos wirkender Sicherheits-Sensor |
Einschlägige Richtlinien: | Maschinenrichtlinie | 2006/42/EG |
RED-Richtlinie | 2014/53/EU | |
RoHS-Richtlinie | 2011/65/EU |
Angewandte Normen: | EN 60947-5-3:2013 ISO 14119:2013 EN 300 330 V2.1.1:2017 EN ISO 13849-1:2015 EN 61508 Teile 1-7:2010 EN 62061:2005 + AC:2010 + A1:2013 + A2:2015 |
Benannte Stelle der Baumusterprüfung: | TÜV Rheinland Industrie Service GmbH Am Grauen Stein, 51105 Köln Kenn-Nr.: 0035 |
EG-Baumusterprüfbescheinigung: | 01/205/5348.03/20 |
Bevollmächtigter für die Zusammenstellung der technischen Unterlagen: | Oliver Wacker Möddinghofe 30 42279 Wuppertal |
Ort und Datum der Ausstellung: | Wuppertal, 21. Januar 2020 |
Rechtsverbindliche Unterschrift Philip Schmersal Geschäftsführer |
UK Declaration of Conformity |
Company: | K.A. Schmersal GmbH & Co. KG Möddinghofe 30 42279 Wuppertal Germany Internet: www.schmersal.com |
Declaration: | We hereby, under sole responsibility, certify that the hereafter described components both in their basic design and construction conform to the relevant statutory requirements, regulations and designated standards of the United Kingdom. |
Name of the component: | RSS260 |
Type: | See ordering code |
Description of the component: | Non-contact safety sensor |
Relevant legislation: | Supply of Machinery (Safety) Regulations | 2008 |
Radio Equipment Regulations | 2017 | |
The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations | 2012 |
Designated standards: | EN 60947-5-3:2013 EN 300 330 V2.1.1:2017 EN ISO 14119:2013 EN ISO 13849-1:2015 IEC 61508 parts 1-7:2010 |
Approved body for Type Examination: | TÜV Rheinland UK Ltd. 1011 Stratford Road Solihull, B90 4BN ID: 2571 |
Type examination certificate: | 01/205U/5348.00/22 |
UK-Importer / Person authorised for the compilation of the technical documentation: | Schmersal UK Ltd. Paul Kenney Unit 1, Sparrowhawk Close Enigma Business Park Malvern, Worcestershire, WR14 1GL |
Place and date of issue: | Wuppertal, November 2, 2022 |
Authorised signature Philip Schmersal Managing Director |
Schmersal India Pvt. Ltd., Plot No - G-7/1, Ranjangaon MIDC, Tal. - Shirur, Dist.- Pune 412 220
Die genannten Daten und Angaben wurden sorgfältig geprüft. Abbildungen können vom Original abweichen. Weitere technische Daten finden Sie in der Betriebsanleitung. Technische Änderungen und Irrtümer vorbehalten.
Generiert am: 13.01.2025, 14:33