schmersal_s_icon.png

IFL 20-333-10/01K-1847

Item number: 101096600

Downloads

TraceParts CAD Data
ePLAN Data
CADENAS CAD Data
SISTEMA Data
Product type description:

IFL (1)-(2)-(3)(4)(5)(6)


(1)
15Switching distance 15 mm
20Switching distance 20 mm

(2)
333Square design, 112 x 40 x 40 mm

(3)
01Opener (NC)
10Normally open contact (NO)
10/01NO contact / NC contact with wiring compartment
111 NO contact / 1 NC contact antivalent

(4)
withoutCable
DDC 2-wire
AAlternating current/direct current AC/DC

(5)
YProtection class IP65
ZProtection class IP67

(6)
Nn-type
Pp-type
Not all component variants, which are possible according to this order code are available and/or technically feasible.
  • Design 333

Ordering data

Product type description

IFL 20-333-10/01K-1847

Article number (order number)

101096600

eCl@ss number, version 12.0

27-27-40-01

eCl@ss number, version 11.0

27-27-01-01

eCl@ss number, version 9.0

27-27-01-01

ETIM number, version 7.0

EC002714

ETIM number, version 6.0

EC002714

General data

Standards

DIN VDE 0660-208

EN IEC 60947-5-2

Housing construction form

Block

Installation conditions (mechanical)

not flush

Note (Installation condition)

On request: Short-circuit and overload-proof.

Housing material

Plastic

Active area

Plastic

Material of the housing cover

Luran

Gross weight

160 g

General data - Features

Integral system diagnostics, status

Yes

Mechanical data - Switching distances

Nominal switching distance Sn

20 mm

Note (switching distance)

All switching distances in accordance EN IEC 60947-5-2

Mechanical data - Connection technique

Length of cable

2 m

Termination

Screw terminals M20 x 1.5

Cable section, maximum

2 x 1.5 mm²

Mechanical data - Dimensions

Length of sensor

112 mm

Width of sensor

40 mm

Height of sensor

40 mm

Ambient conditions

Degree of protection

IP65

Ambient temperature

-25 ... +70 °C

Resistance to vibrations

10 … 55 Hz, amplitude 1 mm

Restistance to shock

30 g / 11 ms

Protection class

II

Ambient conditions - Insulation values

Rated impulse withstand voltage Uimp

4 kV

Electrical data

Rated supply frequency, minimum

45 Hz

Rated supply frequency, maximum

65 Hz

Type of voltage range

AC

Operating current, minimum

10 mA

Operating current

150 mA

Switching element

NO contact or NC contact

Protection circuit integrated

inductive interference protection

Switching frequency, approx.

10 Hz

Electrical data - Digital Output

Voltage drop Ud, maximum

7.5 V

Current at Voltage drop Ud

0.5 A

Design of control elements

Two-wire

Current leakage Ir, maximum

1 mA

Status indication

Note (Integral System Diagnostics, status )

yellow LED

Note

Note (General)

Programmable by repositioning the plug-in jumper at the terminal screws

Diagram


K.A. Schmersal GmbH & Co. KG, Möddinghofe 30, 42279 Wuppertal

The details and data referred to have been carefully checked. Images may diverge from original. Further technical data can be found in the manual. Technical amendments and errors possible.

Generated on: 16/07/2025, 10:55