SFB-PN-IRT-8M12-IOP-V2
SFB-PN-IRT-8M12-IOP-V2
- Safety fieldbox for PROFINET/PROFIsafe
- For connection of up to 8 safety switching devices
- Integrated dual-port switch, IRT-capable
- Protection class IP67
Ordering data
Product type description |
SFB-PN-IRT-8M12-IOP-V2 |
Article number (order number) |
103040357 |
EAN (European Article Number) |
4030661561554 |
eCl@ss number, version 12.0 |
27-24-26-04 |
eCl@ss number, version 11.0 |
27-24-26-04 |
eCl@ss number, version 9.0 |
27-24-26-04 |
ETIM number, version 7.0 |
EC001599 |
ETIM number, version 6.0 |
EC001599 |
Approvals - Standards
Certificates |
TÜV cULus UKCA |
General data
Standards |
EN IEC 61131-1 EN IEC 61131-2 EN ISO 13849-1 EN IEC 60947-5-3 EN IEC 61508 |
Housing material |
Kunststof, polyamide PA 6 GF |
Material of the identification label |
Kunststof, polyamide PA |
Material of viewing window |
Polyamide PACM 12 |
Material of electronic encapsulation |
Polyurethaan 2K PU |
Gross weight |
655 g |
General data - Features
Integral system diagnostics, general |
Ja |
Safety classification |
Vorschriften |
EN ISO 13849-1 EN IEC 61508 |
Safety classification - Safety inputs 2-channels |
Performance Level, up to |
e |
Category |
4 |
Diagnostic Coverage (DC) Level |
99 % |
PFH value |
1,10 x 10⁻⁹ /h |
PFDavg |
9,60 x 10⁻⁵ |
Safety Integrity Level (SIL), suitable for applications in |
3 |
Mission time |
20 Year(s) |
Response time of local safety input ⇒ Fieldbus, maximum |
20 ms |
Notice |
De SFB beantwoordt aan de vereisten als PDDB (naderingsschakelaar met gedefinieerd gedrag in foutomstandigheden) volgens EN 60947-2-3 in combinatie met magneetsensoren (2 NG-contacten) tot PL e/SIL 3. |
Safety classification - Safety inputs 1-channel |
Performance Level, up to |
d |
Category |
2 |
Diagnostic Coverage (DC) Level |
90 % |
PFH value |
2,30 x 10⁻⁷ /h |
PFDavg |
2,00 x 10⁻² |
Safety Integrity Level (SIL), suitable for applications in |
1 |
Mission time |
20 Year(s) |
Response time of local safety input > Fieldbus, maximum |
20 ms |
Test interval for error detection |
10 s |
Safety classification - Safety outputs 1-channel |
Performance Level, up to |
d |
Category |
3 |
Diagnostic Coverage (DC) Level |
90 % |
PFH value |
1,00 x 10⁻⁷ /h |
PFDavg |
8,80 x 10⁻³ |
Safety Integrity Level (SIL), suitable for applications in |
2 |
Mission time |
20 Year(s) |
Reaction time Fieldbus > local safety output |
50 ms |
Safety classification - Safety outputs 2-channels |
Performance Level, up to |
e |
Category |
4 |
Diagnostic Coverage (DC) Level |
99 % |
PFH value |
1,20 x 10⁻⁹ /h |
PFDavg |
1,10 x 10⁻⁴ |
Safety Integrity Level (SIL), suitable for applications in |
3 |
Notes (Safety Integrity Level) |
This product must only be replaced in the application by an identical product of type SFB-PN-IRT-8M12-IOP-V2 with part no. 103040357. The older product version has a lower safety level. |
Mission time |
20 Year(s) |
Reaction time Fieldbus > local safety output |
50 ms |
Mechanical data
Mounting |
Schroeven |
Type of the fixing screws |
2x M6 |
Tightening torque of the fixing screws, maximum |
3 Nm |
Type of the fixing screws, viewing window |
2x TX10 (Torx) |
Tightening torque of the fastening screws for the viewing window, maximum |
0,6 Nm |
Mechanical data - Connection technique
Termination |
M12 Inbouwstekker / -stekker |
Terminal connector, Input/Output |
X0 - X7: M12, 8-polig, A-codering |
Terminal Connector, Power I/O |
M12 POWER, 4-polig, T-codering |
Terminal Connector, Field bus |
M12, 4-polig, D-codering |
Tightening torque of electrical connection, minimum |
0,8 Nm |
Tightening torque of electrical connection, maximum |
1,5 Nm |
Mechanical data - Dimensions
Length |
222,8 mm |
Width |
63 mm |
Height |
36,1 mm |
Ambient conditions
Degree of protection |
IP66 IP67 |
Ambient temperature |
-25 ... +55 °C |
Storage and transport temperature |
-25 ... +70 °C |
Relative humidity, minimum |
10 % |
Relative humidity, maximum |
95 % |
Note (Relative humidity) |
niet-condenserend |
Resistance to vibrations |
10 … 150 Hz, Amplitude 0,35 mm / 5 g |
Restistance to shock |
30 g / 11 ms |
Protection class |
III |
Permissible installation altitude above sea level, maximum |
2.000 m |
Ambient conditions - Insulation values
Rated insulation voltage Ui |
32 VDC |
Rated impulse withstand voltage Uimp |
0,8 kV |
Overvoltage category |
III |
Degree of pollution |
3 |
Electrical data
Operating voltage |
24 VDC -15 % / +10 % |
Current consumption |
200 mA |
Rated operating voltage |
24 VDC |
Operating current |
10.000 mA |
Note (Electrical data, Fuse rating) |
Externe beveiliging vereist ≤ 10A traag bij gebruik volgens UL 61010. |
Time to readiness, maximum |
8.000 ms |
Device Watchdog Time |
10 ms |
Device Acknowledgement Time, maximum |
25 ms |
Reaction Time Safety Input, maximum |
20 ms |
Reaction Time Safety Output, maximum |
50 ms |
Electrical data - Communication protocols
Feldbus Protokoll |
PROFINET / PROFIsafe |
Fieldbus specification |
V2.3, Conformance Class C |
Specification safety fieldbus |
V2.4 |
Fieldbus properties |
Media Redundancy Protocol (MRP) Fast Start Up |
Fieldbus network load class |
3 |
Transfer rate |
100 Mbit/s Full Duplex |
Adressing |
Discovery and Configuration Protocol (DCP) |
Integrated switch |
Dual Port, 100 Mbit/s, IRT capable |
Fieldbus services |
I&M0 ... I&M3, SNMP, LLDP |
Service interface |
WEB-Interface HTTP |
Electrical data - Device Ports
Bezeichnung, Geräteanschlüsse |
X0 ... X7 |
Cable length, device port |
30 m |
Electrical data - Power supply external devices
Designation, Power supply |
A1 and A2 |
Rated operating voltage |
24 VDC |
Rated operating current |
800 mA |
Internal electrical fuse |
1.5 A (Integrated automatic resettable fuse) |
Electrical data - Safety digital inputs
Designation, Safety inputs |
X1 en X2 |
Switching thresholds |
−3 V … 5 V (Low) 13 V ... 30 V (High) |
Current consumption at 24 V |
6 mA |
Permissible residual drive current |
1 mA |
Test pulse duration, minimum |
0,01 ms |
Test pulse duration, maximum |
1 ms |
Test pulse interval, minimum |
20 ms |
Test pulse interval, maximum |
120.000 ms |
Classification ZVEI CB24I, Sink |
C1 |
Classification ZVEI CB24I, Source |
C1 C2 C3 |
Electrical data - Safety digital outputs
Designation, Safety outputs |
DO |
Design of control elements |
kortsluitvast, p-schakelend |
Voltage drop Ud, maximum |
2 V |
Leakage current Ir, maximum |
0,5 mA |
Voltage, Utilisation category DC-12 |
24 VDC |
Current, Utilisation category DC-12 |
0,8 A |
Voltage, Utilisation category DC-13 |
24 VDC |
Current, Utilisation category DC-13 |
0,8 A |
Note, Utilisation category DC-13 |
Inductive load, maximum 400 mH |
Switching frequency, maximum |
1 Hz |
Test pulse duration, maximum |
1 ms |
Test pulse interval, minimum |
15 ms |
Test pulse interval, maximum |
500 ms |
Classification ZVEI CB24I, Source |
C1 |
Classification ZVEI CB24I, Sink |
C1 |
Electrical data - Diagnostic inputs / FB-Interface
Designation, Diagnostic inputs / FB-Interface |
DI |
Switching thresholds |
−3 V … 5 V (Low) 15 V … 30 V (High) |
Current consumption at 24V |
12 mA |
Input debounce filter |
10 ms |
Data transfer rate FB-Interface |
19,2 kBaud |
Electrical data - Test pulse output
Designation, Test pulse outputs |
Y1 and Y2 |
Design of control elements |
kortsluitvast, p-schakelend |
Voltage drop Ud, maximum |
1 V |
Current leakage Ir, maximum |
0,5 mA |
Voltage, Utilisation category DC-12 |
24 VDC |
Y1 rated current at 24 V |
15 mA |
Y2 rated current at 24 V |
10 mA |
Y2 rated current at 0 V |
30 mA |
Test pulse interval, typical |
500 ms |
Test pulse duration, maximum |
1 ms |
Classification ZVEI CB24I, Sink |
C1 |
Classification ZVEI CB24I, Source |
C1 |
LED status display - LED 01
LED status |
Error-LED toestelaansluiting |
LED position |
E: 0 ... 7 |
LED colour |
groen/rood |
LED status display - LED 02
LED status |
Input-LED toestelaansluiting |
LED position |
I: 0 ... 7 |
LED colour |
geel |
LED status display - LED 03
LED status |
Link-LED Ethernet-poort |
LED position |
L: P1 + P2 |
LED colour |
groen |
LED status display - LED 04
LED status |
Activity-LED Ethernet-poort |
LED position |
A: P1 + P2 |
LED colour |
geel |
LED status display - LED 05
LED status |
Systeemfout LED |
LED position |
"SF": module |
LED colour |
groen/rood |
LED status display - LED 06
LED status |
Busfout LED |
LED position |
"BF": module |
LED colour |
rood |
LED status display - LED 07
LED status |
Error-LED veldbus |
LED position |
"Err": module |
LED colour |
groen/rood |
LED status display - LED 08
LED status |
Power-LED veldbox |
LED position |
"Pwr": module |
LED colour |
groen |
Other data
Note (applications) |
Veilige veldbus met remote I/O's |
Taalfilter
Datasheet
Bedieningshandleiding en conformiteitsverklaring
Getting started
Systeemhandboek
Goedkeuringscertificaat
UL-certificaat
UKCA Certificaat
Bestanden met de toestelbeschrijving
Configuratiesoftware (document met link)
Brochure
Algemene informatie
SISTEMA-VDMA-bibliotheek/library
Download de nieuwste versie van Adobe Reader
Foto van het product (individuele catalogusfoto)
Maatschets basistoestel
EU-conformiteitsverklaring | ![]() |
Original | K.A. Schmersal GmbH & Co. KG Möddinghofe 30 42279 Wuppertal Germany Internet: www.schmersal.com |
Verklaring: | Hiermee verklaren wij dat de hieronder beschreven producten op grond van hun ontwerp en constructie beantwoorden aan de relevante Europese Richtlijnen. |
Benaming van de component: | SFB |
Type: | zie bestelsleutel |
Beschrijving van de component: | Veilige veldbox (IO-module met veldbusinterfaces) |
Geharmoniseerde Richtlijnen: | Machinerichtlijn | 2006/42/EG |
EMC-Richtlijn | 2014/30/EU | |
RoHS-Richtlijn | 2011/65/EU |
Toegepaste normen: | EN 61131-2:2007 EN 60947-5-3:2013 EN ISO 13849-1:2015 IEC 61508 Deel 1-7:2010 |
Bevoegde installatie voor de typekeuring: | TÜV Rheinland Industrie Service GmbH Am Grauen Stein, 51105 Köln Kenn Nr.: 0035 |
EG-Goedkeuringscertificaat: | 01/205/5878.00/22 |
Gemachtigde voor het samenstellen van de technische documentatie: | Oliver Wacker Möddinghofe 30 42279 Wuppertal |
Plaats en datum van opstelling: | Wuppertal, 4 mei 2022 |
![]() |
Rechtsgeldige handtekening Philip Schmersal Directeur |
UK Declaration of Conformity | ![]() |
Company: | K.A. Schmersal GmbH & Co. KG Möddinghofe 30 42279 Wuppertal Germany Internet: www.schmersal.com |
Declaration: | We hereby, under sole responsibility, certify that the hereafter described components both in their basic design and construction conform to the relevant statutory requirements, regulations and designated standards of the United Kingdom. |
Name of the component: | SFB-PN-IRT SFB-EIP |
Type: | See ordering code |
Description of the component: | Safety fieldbox (IO module with fieldbox interface) |
Relevant legislation: | Supply of Machinery (Safety) Regulations | 2008 |
Electromagnetic Compatibility Regulations | 2016 | |
The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations | 2012 |
Designated standards: | EN 61131-2:2007 EN 60947-5-3:2013 EN ISO 13849-1:2015 EN 61508 parts 1-7:2010 |
Approved body for Type Examination: | TÜV Rheinland UK Ltd. 1011 Stratford Road Solihull, B90 4BN ID: 2571 |
Type examination certificate: | 01/205U/5878.01/23 |
UK-Importer / Person authorised for the compilation of the technical documentation: | Schmersal UK Ltd. Paul Kenney Unit 1, Sparrowhawk Close Enigma Business Park Malvern, Worcestershire, WR14 1GL |
Place and date of issue: | Wuppertal, October 16, 2023 |
![]() |
Authorised signature Philip Schmersal Managing Director |
Schmersal India Pvt. Ltd., Plot No - G-7/1, Ranjangaon MIDC, Tal. - Shirur, Dist.- Pune 412 220
De genoemde gegevens en informatie zijn zorgvuldig gecontroleerd. Afbeeldingen kunnen afwijken van het origineel. Verdere technische gegevens zijn te vinden in de handleiding. Technische wijzigingen en fouten voorbehouden.
Gegenereerd op 11-04-2025 00:15